| 2021-05-26 11:11:08 | ZONING PLAN REVIEW |
| | ________________________________________ |
| | |
| | DATE OF REVIEW: 5/25/2021 |
| | ________________________________________ |
| | |
| | REVIEW STATUS: FAILED |
| | ________________________________________ |
| | |
| | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN |
| | REVIEW COMMENTS: |
| | |
| | 1. PROVIDE THE SETBACKS OF THE PROPOSED GENERATOR TO |
| | ALL PROPERTY LINES. PER THE CITY ZONING CODE, |
| | MECHANICAL EQUIPMENT CANNOT ENCROACH MORE THAN 4 FEET |
| | INTO A REQUIRED SETBACK. IN THIS CASE, THE GENERATOR |
| | MUST BE SETBACK A MINIMUM OF 1 FOOT FROM THE SIDE |
| | PROPERTY LINE AND 11 FEET FROM THE REAR PROPERTY |
| | LINE.. |
| | 2. PER THE FLORIDA BUILDING CODE, GENERATOR EXHAUST |
| | MUST BE A MINIM OF 10 FEET AWAY FROM ANY DOORS AND |
| | WINDOW OPENINGS. |
| | ________________________________________ |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD |
| | LIKE TO RESUBMIT ELECTRONICALY, EMAIL |
| | [email protected] AND REQUEST TO HAVE YOUR |
| | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN |
| | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. |
| | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU |
| | ARE FINISHED UPLOADING. |
| | |
| | ________________________________________ |
| | |
| | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: |
| | |
| | RAFAELA THERMIDOR, ASSOCIATE PLANNER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION |
| | 401 CLEMATIS STREET - P.O. BOX 3147 |
| | WEST PALM BEACH, FLORIDA 33402 |
| | |
| | TTY: 800.955.8771 |
| | E: [email protected] |
| | W: WPB.ORG |
| | |