| Plan Review Notes For Permit 21050649 |
| Permit Number |
21050649 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-07-02 10:23:14 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | NO CHANGES SINCE THE LAST REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) FLAME SPREAD TEST REPORT PROVIDED IS FOR A TILE | | | FLOOR - NEED THE FLAME SPREAD TEST REPORT FOR A WOOD | | | FLOOR - THE FOLLOWING ACUSTICAL TEST REPORTS ARE | | | REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY | | | BEFORE RESUBMITTING TO PROJECTDOX ( [email protected] | | | ) | | | 3) THE DRAWINGS SHOW THAT "SUPER SAM 125" IS TO BE USED | | | - THE DRAWINGS WILL NEED TO BE REVISED IF THE PRODUCT | | | IS CHANGED, | | | |
|