| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R7 SELECTED SYSTEM NO W-4; EXPOSURE |
| | (B); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ZONES 1 |
| | PRIME, 1, 2, & 3; ULTIMATE WIND SPEED (160), IS NOT |
| | CORRECT. THE ULTIMATE WIND SPEED FOR THE LISTED ADDRESS |
| | IS 170 (MPH). PLEASE SELECT THE CORRECT OPTIONS; |
| | CONSIDER USING SYSTEM NO. W-4; EXPOSURE C; ZONES 1 |
| | PRIME, 1, 2, & 3; ENCLOSED; H < 15; 180 (MPH). |
| | 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL16709-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY. SECOND |
| | REQUEST. |
| | |