| 2021-09-03 11:08:25 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE UNDERSTAND THAT WE CANNOT USE THE |
| | ARCHITECTURAL OCCUPANT COUNT TO DETERMINE THE OUTDOOR |
| | AIR FOR THE TENANT SPACE. SEE BELOW PLEASE PROVIDE |
| | OUTDOOR AIR CALCULATIONS BASED ON FBC M 403.3.1.1 AND |
| | TABLE 403.3.1.1. FOOTNOTE (A) CAN AND SHOULD BE USED. |
| | (EXAMPLE- SHOWROOM 9500 SQ. FT. 9500/1000 = 9.5; 9.5 X |
| | 15 = 143 OCCUPANTS. 143 X 7.5 = 1,072.5 CFM; 9500 X .12 |
| | = 1,140; 1,072.5 + 1,140 = 2,212.5 CFM OF OUTDOOR AIR |
| | REQUIRED FOR THE SHOWROOM. |
| | |
| | 403.3.1.1 OUTDOOR AIRFLOW RATE. VENTILATION SYSTEMS |
| | SHALL BE DESIGNED TO HAVE THE CAPACITY TO SUPPLY THE |
| | MINIMUM OUTDOOR AIRFLOW RATE, DETERMINED IN ACCORDANCE |
| | WITH THIS SECTION. IN EACH OCCUPIABLE SPACE, THE |
| | VENTILATION SYSTEM SHALL BE DESIGNED TO DELIVER THE |
| | REQUIRED RATE OF OUTDOOR AIRFLOW TO THE BREATHING ZONE. |
| | THE OCCUPANT LOAD UTILIZED FOR DESIGN OF THE |
| | VENTILATION SYSTEM SHALL BE NOT LESS THAN THE NUMBER |
| | DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD |
| | RATE INDICATED IN TABLE 403.3.1.1. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |