| Plan Review Notes For Permit 21050626 |
| Permit Number |
21050626 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-08-10 12:35:22 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050626 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS BASED ON FBC | | | 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE ARCHITECTURAL | | | OCCUPANT NUMBERS AS 403.3.1.1 TELLS US WE MUST USE | | | TABLE 403.3.1.1. PLEASE ALSO REMEMBER YOU CAN USE THE | | | FOOTNOTES TO THE TABLE WHERE THEY APPLY (FOOTNOTE A | | | ALLOWS THE USE OF NET SQ. FT. INSTEAD OF GROSS). | | | | | | 2) PLEASE UPLOAD THE MECHANICAL EQUIPMENT SIZING | | | CALCULATION SEPARATELY INTO SUPPORTING DOCS. IF ONE | | | NEEDED TO SEE THEM AT A LATER DATE IT WOULD NOT BE KNOW | | | THAT THEY WERE UPLOADED WITH THE REVIEW COMMENTS. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|