| 2021-06-30 13:10:18 | 06/30/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A0.0 UNDER CODE / PROJECT INFORMATION, |
| | PLEASE PROVIDE THE CORRECT EDITION FOR ALL FLORIDA |
| | CODES PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 2. ON SHEET A0.2; |
| | |
| | A. DETAIL 18 THE SIDEWALL AND DISPENSER OUTLET |
| | LOCATION, GRAB BAR SHOWS A VERTICAL GRAB BAR. GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION PER THE |
| | 2020 FBC ACC SEC. 609.4. |
| | |
| | B. DETAIL 8 THE DRINKING FOUNTAIN DETAIL IS MISSING THE |
| | DIMENSION OF 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING |
| | FOUNTAIN PER THE 2020 FBC ACC SEC. 602.2 CLEAR FLOOR |
| | SPACE. |
| | |
| | C. ON NOTE #1, IT HAS AN EXCEPTION FOR ICC/ANSI |
| | A117.1-2009. HOWEVER, UNDER THE CODE REFERENCE, THIS IS |
| | NOT NOTED. IN DETAIL #4, NOTE 3 HAS 2010 MENTION PLEASE |
| | CORRECT THE CODE CYCLE AND CODE REFERENCE ON THE |
| | ACCESSIBLE 2020 FBC PER WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON THE SHEET, A1.1 DOES NOT SHOW THE KITCHEN CLEAR |
| | FLOOR SPACE FOR THE BREAKROOM SINK. PLEASE PROVIDE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. ON SHEET A6.0; |
| | |
| | A., PLEASE GIVE THE CLEAR FLOOR SPACE FOR THE DRINKING |
| | FOUNTAIN PER THE 2020 FBC ACC SEC. 602.2 CLEAR FLOOR |
| | SPACE. |
| | |
| | B. ON DETAIL #1 AND #4, SHOW A VERTICAL GRAB BAR. GRAB |
| | BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION PER |
| | THE 2020 FBC ACC SEC. 609.4. |
| | |
| | C. ON THAT SAME DETAIL, THE GRAB BARS ON A HORIZONTAL |
| | SHALL BE MEASURED TO THE CENTER OF THE BAR PER THE 2020 |
| | FBC ACC SEC. 604.5.1 SIDE WALL AND 604.5.2 REAR WALL. |
| | |
| | D. ON THAT SAME DETAIL, THE WATER CLOSET PAPER |
| | DISPENSER IS 12,? AND IT SHALL BE 7? INCHES MINIMUM AND |
| | 9? INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED |
| | TO THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC |
| | SEC. 604.7. |
| | |
| | E. DETAIL #4 SHOWS THE HANDLE NOT ON THE OPEN SIDE FOR |
| | FLUSH CONTROL SHALL BE HAND OPERATED ON THE OPEN SIDE |
| | PER THE 2020 FBC ACC SEC. 604.9.5. |
| | |
| | F. PLEASE SHOW DIMENSIONS FOR GRAB BARS LIKE ON-PAGE |
| | A0.2 OR PUT A NOTE TO REFER TO #8 DETAIL ON THE UNDER |
| | GENERAL NOTES THAT ARE MORE SPECIFIC TO WHERE TO FIND |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | G. THE SAME FOR THE LAV ON DETAIL #3 SHOW DIMENSION FOR |
| | UNDER LAV ARE MISSING DIMENSIONS AND NOT SHOWN ON |
| | ADDITIONAL ACCESSIBILITY INFORMATION. PLEASE PROVIDED |
| | ACCORDING TO 2020 FBC ACC. |
| | |
| | H. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5. |
| | |
| | I. PLEASE PROVIDE CABINET DETAIL SHOWING THE KITCHEN |
| | SINK HEIGHT OF 34? INCHES MAXIMUM PER THE 2017 FBC ACC |
| | SEC. 606.3. |
| | |
| | K. PLEASE SHOW KITCHEN CLEAR FLOOR SPACE DIMENSION FOR |
| | BREAKROOM SINK. IN ADDITION, PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | L. PLEASE SHOW FOR WATER FOUNTAIN THE SHOW KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE 2020 |
| | FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH 2017 |
| | FBC ACC SEC. 307.2 PROTRUSION LIMITS. |
| | |
| | 5. PLEASE PROVIDE A SLAB REPAIR DETAIL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. ON SHEET P0.0; |
| | |
| | A. UNDER THE STANDARD CODE # B, IT REFERS TO THE 2017 |
| | FBC CODE AND 2015. PLEASE CORRECT THE CORRECT YEAR AND |
| | DELETE 2015 IPC PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE |
| | NONMETALLIC PIPPING THROUGH RATED WALLS AND THE FLOORS. |
| | IN ADDITION, PLEASE SUBMIT THE COMPLETE ASSEMBLY |
| | DETAILS FOR THE UL 449 AND 605 SYSTEMS PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | C. PLUMBING ENERGY NOTES 1-5 DOES NOT APPLY TO THE |
| | PLUMBING SYSTEM. PLEASE REMOVE OR X OUT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON THE PLUMBING FIXTURE SCHEDULE WB-1 WALL BOX FOR |
| | WATER, IS IT IN A FIREWALL, AND IF SO, PLEASE PROVIDE A |
| | FIRE-RATED BOX RATING PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. IF APPLICABLE |
| | |
| | F. UNDERGROUND PIPES AND NOT IN CONDITION SPACE NEED TO |
| | BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. |
| | RE 403.5.3. |
| | |
| | 7. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM |
| | FOR SANITARY AND WATER PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 8. ON THE SHEET, P1.0 SHOWS THE BATHROOM GROUPS ON |
| | THROUGH THE TRUNK LINE, WHICH ENDS UP ON THE DRINKING |
| | FOUNTAIN DRAIN; THIS CANNOT DISCHARGE INTO A HORIZONTAL |
| | WET VENT PER THE 2020 FBC SEC. P 912.1. SUGGESTION, |
| | ISOLATE BATHROOM GROUPS AND USE TRUNK LINE AS A DIRECT |
| | DISCHARGE TO SEPARATE BOTH SYSTEMS. |
| | |
| | 9. ON SHEET P1.1, THE FW-1 MAY REQUIRE A BACKFLOW |
| | DEVICE PER MANUFACTURE IS SO IT SHALL BE AN INLINE |
| | VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024 |
| | NON-CARBONATED. PLEASE SHOW THE HAMMER ARRESTOR FOR |
| | THIS ITEM AND DRINKING FOUNTAIN THE 2020 FBC P 604.9. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE |
| | YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |