| Plan Review Notes For Permit 21050545 |
| Permit Number |
21050545 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2022-09-29 16:24:54 | BUILDING REVIEW APPROVED WITH PROVISO. | | | (NOTE: SUBMIT INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | | | | 1-REVISE MAIN HOUSE ENERGY CALCULATIONS: MISSING | | | WINDOWS ON THE EAST SIDE. SEE FLOOR PLAN. | | | 2- REVISE REAR STRUCTURE ENERGY CALCULATIONS WINDOWS | | | INFORMATION: GLASS DOORS SQUARE FOOTAGE DOESN'T MATCH | | | PLANS. | | | 3- PROVIDE PRODUCT APPROVAL FOR (NOTE: SUBMIT | | | INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION | | | TO AVOID CONFLICTS/DEALAYS): | | | A)DEN FRENCH DOORS NOA THAT MEET OR EXCEED THE DESIGN | | | PRESSURES SHOWN ON PLANS. | | | B)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). | | | C)HURRICANE SHUTTERS FOR DOORS WITHOUT IMPACT GLAZING. | | | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | D)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | TO BE INSTALLED (NOTE: WOOD ROOF & CONCRETE BALCONY). | | | |
|