Plan Review Notes
Plan Review Notes For Permit 21050545
Permit Number 21050545
Review Stop P
Sequence Number 3
Notes
Date Text
2022-05-19 11:32:043RD REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21050545
 5/19/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 3RD REQUEST- SHEET P-1: PLEASE REVIEW DEFINITIONS OF
 BUILDING DRAIN AND BUILDING SEWER- SEC. 202 FBC RES AND
 CORRECT THE PLANS TO SHOW THE LOCATIONS OF THE REQUIRED
 CLEANOUTS AT EACH DRAIN/SEWER JUNCTION- SEE SECS.
 P3005.2.3 & P3005.2.3 FBC RES.
  
 2) DUE TO A CHANGE IN PROCESS, THE A POTABLE WATER
 SERVICE BACKFLOW PERMIT IS REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION ?TBD? (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 3) PREVIOUS REVIEW COMMENT- TWO DWELLINGS ON THE SAME,
 OR CONSTRUCTION OF A COMMERCIAL BUILDING ON THE
 PROPERTY WILL REQUIRE INSTALLATION OF A POTABLE WATER
 SERVICE BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH
 THE WPB DEPT. OF UTILITIES CROSS-CONNECTION CONTROL
 MANUAL. PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED
 TO INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT
 THE WATER METER- SECS. C & E WPB CROSS-CONNECTION
 MANUAL.
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  