| 2022-06-02 11:06:29 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE DETAIL SMOKE/CARBON ALARM AT FIRST FLOOR OF |
| | GARAGE STRUCTURE. FBC 553.883 |
| | 2) IT APPEARS GUEST HOUSE/GARAGE DETAILS MORE THAN ONE |
| | MULTI WIRE CIRCUIT/FEEDER NOT IN COMPLIANCE WITH NEC |
| | 225.30. PLEASE INDICATE THAT GUEST HOUSE HAS SUBPANEL |
| | FOR GUEST HOUSE LOADS. AS PER NEC 225.30. IN ADDITION, |
| | PROVIDE A GROUNDING ELECTRODE SYSTEM AT SEPARATE |
| | BUILDING. NEC 250.32 |
| | 3) PLEASE LOCATE ELECTRIC PANEL ON FLOOR PLAN TO BE IN |
| | COMPLIANCE WITH NEC 110.26 (A)(1) |
| | 4) PLEASE DETAIL THE REQUIRED RECEPTACLES AT, MAIN |
| | HOUSE AND GARAGE, NEXT TO ALL OUTSIDE AIR CONDITIONING |
| | EQUIPMENT AS REQUIRED BY NEC 210.63 |
| | 5) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AS |
| | REQUIRED PER NEC 210.52(E)(3) AND 210.52 (G)(2) AT |
| | GARAGE |
| | 6) PLEASE DETAIL THE REQUIRED RECEPTACLE AT THE END OF |
| | KITCHEN PENINSULAR AS REQUIRED PER NEC 210.52 (C)(3) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |