| 2022-07-05 11:21:26 | NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21050545 |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5.1 FBC-ENERGY CONSERVATION. |
| | NOTE: NEED TWO SEPARATE ENERGY CALCULATIONS. ONE FOR |
| | THE MAIN HOUSE AND ONE FOR THE REAR STRUCTURE. |
| | PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE |
| | REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| | AGENT TO AVOID CONFLICT/DELAYS. |
| | BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REVISE MAIN HOUSE ENERGY CALCULATIONS: |
| | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER (THIS JURISDICTION IS 604700). SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)CEILING INFORMATION ON ITEM #11 OF PAGE 1 DOESN'T |
| | MATCH PLANS. COORDINATE WITH ARCHITECT TO AVOID MORE |
| | CONFLICTS/DELAYS AND REVISE AS REQUIRED. |
| | NOTE: COORDINATE WITH ITEM #9 BELOW. ARCHITECT IS NOT |
| | SPECIFYING UNVENTED ATTIC. ARCHITECT NEEDS TO SPECIFY |
| | ATTIC VENTILATION AS REQUIRED BY SEC. R806.1 |
| | FBC-RESIDENTIAL. |
| | |
| | C)PROJECT INFORMATION ON PAGE 2 IS INCORRECT. THE MAIN |
| | HOUSE IS ONE STORY NOT TWO STORY. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) REVISE/CLARIFY NUMBER OF OCCUPANTS SPECIFIED ON PAGE |
| | TWO UNDER SPACES. |
| | THIS IS A 3 BEDROOM HOUSE. CLARIFY WHY LIMITING THE USE |
| | OF THIS HOUSE TO ONLY TWO OCCUPANTS?. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION |
| | TO MATCH PLANS. |
| | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE |
| | WINDOWS GLAZING SECTION. |
| | |
| | REVISE REAR STRUCTURE ENERGY CALCULATIONS: |
| | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER (THIS JURISDICTION IS 604700). SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)FLOOR INFORMATION ON ITEM #9 ON PAGE ONE DOESN'T |
| | MATCH PLANS. NEED INSULATION BETWEEN A/C AND NON A/C |
| | AREAS. ALSO, REVISE A/C SQUARE FOOTAGES. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C)CEILING INFORMATION ON ITEM #11 OF PAGE 1 DOESN'T |
| | MATCH PLANS. COORDINATE WITH ARCHITECT TO AVOID MORE |
| | CONFLICTS/DELAYS AND REVISE AS REQUIRED. |
| | NOTE: ARCHITECT IS NOT SPECIFYING UNVENTED ATTIC. |
| | ARCHITECT NEEDS TO SPECIFY ATTIC VENTILATION AS |
| | REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| | |
| | D)THERE IS NOT KITCHEN IN THIS STRUCTURE. SEE PLANS AND |
| | REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)DOORS INFORMATION IS INCORRECT. THERE ARE NO SOLID |
| | WOOD DOORS IN THE REAR STRUCTURE. SEE PLANS AND REVISE |
| | AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION |
| | TO MATCH PLANS. ALSO, MAKE SURE ALL WINDOWS ARE |
| | INCLUDED IN THE CALCULATIONS. SEE PLANS. |
| | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE |
| | WINDOWS GLAZING SECTION. |
| | |
| | 2- OK. |
| | 3- OK. |
| | 4- OK. |
| | 5- OK. |
| | |
| | 6- DEFERRED SUBMITTAL: |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR |
| | A)ALL WINDOWS AS SPECIFIED ON PLANS. |
| | B)ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. |
| | C)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). |
| | D)OVERHEAD GARAGE DOOR. |
| | E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | F) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | 7- OK. |
| | 8- OK. |
| | |
| | 9- ARCHITECT IS NOT DESIGNING AN UNVENTED ATTIC. |
| | COORDINATE WITH ENERGY CALCULATIONS COMMENTS. ARCHITECT |
| | NEEDS TO SPECIFY ATTIC/ROOF VENTILATION AS REQUIRED BY |
| | SEC. R806.1 FBC-RESIDENTIAL. |
| | NOTE: FIRST FLOOR PLAN ON SHEET A-1 SPECIFIES R-20 |
| | ICYNENE INSULATION ABOVE GARAGE. IF ARCHITECT IS |
| | DESIGNING AN UNVENTED ATTIC, THEN ICYNENE INSULATION |
| | MAY BE USED ON MAIN HOUSE AND SECOND FLOOR ROOF ALSO. |
| | IF SO, REVISE PLANS/SECTIONS ACCORDINGLY. |
| | |
| | 10- DRAWINGS M1, M2, E1 NEED ARCHITECT'S ORIGINAL |
| | DIGITAL SIGNATURE. DRAWINGS S1 THRU S9 NEED ENGINEER'S |
| | ORIGINAL DIGITAL SIGNATURE. |
| | ALSO, THE GEOTECHNICAL REPORT AND SURVEY NEED THE |
| | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. |
| | CHAPTER 481, CHAPTER 471 FLORIDA STATUTES. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |