| 2022-02-01 14:45:52 | 2ND REVIEW FBC-2020 RES. |
| | PERMIT- 21050545 |
| | 2/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FORM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS. |
| | |
| | 1) FAILED. SHEET A2: REFER TO SECTION 903.4.1 & 903.4.2 |
| | FBC RES AND SHOW OVERFLOW SCUPPER LOCATIONS. PROVIDE |
| | SIZING CALCULATIONS FOR BOTH THE PRIMARY AND THE |
| | OVERFLOW SCUPPERS AND PROVIDE CONSTRUCTION DETAILS. |
| | REFER TO SECTIONS 1106.1- 1108.3 FBC P FOR FURTHER |
| | REQUIREMENTS. THE OVERFLOW SCUPPERS WERE NOT PROVIDED |
| | AS REQUIRED. |
| | |
| | 2) FAILED. P1: CLEANOUTS ARE REQUIRED AT THE JUNCTIONS |
| | OF THE BUILDING DRAINS AND SEWER LINE AND SHALL BE |
| | LOCATED AT THE JUNCTIONS OR A MAXIMUM OF 10 FT. |
| | DEVELOPED LENGTH OF PIPING UPSTREAM OF THE JUNCTIONS- |
| | SECTION- P3005.2.3 FBC RES. PLEASE NOTE THE DEFINITION |
| | OF BUILDING DRAIN: THE LOWEST PIPING THAT COLLECTS THE |
| | DISCHARGE FROM ALL OTHER DRAINAGE PIPING INSIDE THE |
| | HOUSE AND EXTENDS 30 INCHES IN DEVELOPED LENGTH OF |
| | PIPE, BEYOND THE EXTERIOR WALLS AND CONVEYS THE |
| | DRAINAGE TO THE BUILDING SEWER. A) THE CLEANOUTS WERE |
| | NOT PROVDED AS REQUIRED. B) THE MASTER BATH DRAIN AND |
| | VENT SYSTEM IS NON-COMPLIANT. C) VENTS ARE MISSING FOR |
| | THE KITCHEN SINK, WASHING MACHINE AND FLOOR DRAIN. |
| | PLEASE REFER TO SECTION P3108.1- P3108.3 FBC RES: |
| | DESIGN THE MASTER BATH WET VENT SIMILAR TO THE 1ST |
| | FLOOR BATH VENT WITH ALL FIXTURE DRAINS CONNECTING TO |
| | ONE BRANCH EXITING THE BUILDING TO THE SEWER DRAIN. THE |
| | VENT FOR THE SYSTEM SHALL BE A DRY VENT LOCATED SO THAT |
| | NOT MORE THAN ONE FIXTURE IS LOCATED UPSTREAM OF THE |
| | VENT. CONCERNING RTHE KITCHEN SINK AND DISHWASHER, AN |
| | AIR ADMITTANCE VALVE CAN BE INSTALLED IF THERE IS NO |
| | MEANS OF GETTING A COMPLIANT VENT-TO RIDGE- SEE SECS. |
| | P3106, P3107, AND P3114 FBC RES. CONCERNING THE WASHING |
| | MACHINE AND FLOOR DRAIN, A VENT TO RIDGE FOR THE |
| | WASHING MACHINE FIXTURE DRAIN CAN SERVE AS A COMMON |
| | VENT FOR BOTH FIXTURES- SEC. P3106 FBC RES. |
| | |
| | NEW COMMENT. |
| | |
| | 1) PLEASE NOTE THAT TWO DWELLINGS ON THE SAME LOT WILL |
| | REQUIRE INSTALLATION OF A POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH THE WPB |
| | DEPT. OF UTILITIES CROSS-CONNECTION CONTROL MANUAL. |
| | PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED TO |
| | INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT THE |
| | WATER METER- CHAPTER C (PAGE 12 WPB CROSS-CONNECTION |
| | MANUAL. |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |