Plan Review Notes
Plan Review Notes For Permit 21050545
Permit Number 21050545
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-23 13:45:16NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050545
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: NEED TWO SEPARATE ENERGY CALCULATIONS. ONE FOR
 THE MAIN HOUSE AND ONE FOR THE REAR STRUCTURE.
 PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE
 REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
 BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC-
 ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED GRADE
 ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM ADJACENT
 PROPERTIES, SPECIALLY ON THE EAST SIDE, WHERE THE GRADE
 ELEVATION IS LOWER (SEE SURVEY).
 NOTE: CHECK IF RETAINING WALLS WILL BE REQUIRED.
 COMPLETE DETAILS WILL BE REQUIRED ON A SEPARATE PERMIT.
  
 3- SHEET A-1:
 A)OK.
 B)OK.
  
 ORIGINAL COMMENT:
 C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH
 SEC. R311.7 FBC-RESIDENTIAL. PROVIDE COMPLETE
 INFORMATION FOR RISERS, TREADS, WINDER TREADS,
 HANDRAILS AND GUARDRAILS (INCLUDING BALCONY GUARDRAIL),
 STAIRWAY HEADROOM, ETC.
  
 RESPONSE:
 DETAILS ON SHEET A-2.1:
 (1)STAIR DETAIL PLAN 1/A-2.1 AND DETAIL 3/A-2.1 SHOW
 KNEE-WALLS ON BOTH SIDES OF STAIRWAY. NEED TO SHOW
 COMPLIANCE WITH THE HANDRAILS SEC. R311.7.8
 FBC-RESIDENTIAL. NOTE: CHECK WITH REQUIRED STAIRWAY
 WIDTH SEC. R311.7.1 FBC-RESIDENTIAL.
 (2)WINDERS TO COMPLY WITH SEC. R311.7.5.2.1
 FBC-RESIDENTIAL. SPECIFY DIMENSION OF THE NARROW END OF
 THE WINDER. (6" MIN.)
 (3)TREAD DIMENSION SPECIFIED ON THE STAIR NOTE AND
 TREAD DIMENSION SHOWN ON THE THE STAIR DETAIL PLAN
 1/A-2.1 DON'T MATCH. REVISE AS REQUIRED TO MATCH.
  
  
 ORIGINAL COMMENT:
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DWELLING- GARAGE FIRE SEPARATION AS REQUIRED BY SEC.
 R302.6 FBC-RESIDENTIAL.
  
 RESPONSE:
 FLOOR CEILING ASSEMBLY FIRE RATING NEEDS TO COMPLY WITH
 TABLE R302.6 FBC-RESIDENTIAL.
  
 E) OK.
  
 ORIGINAL COMMENT:
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 RESPONSE:
 STAIR DETAILS ON SHEET A-2.1 REFER TO DRAFSTOPPING.
 DRAFSTOPPING AND FIREBLOCKING ARE TWO SEPARATE
 REQUIREMENTS. SEE SEC. R302.12 FBC-RESIDENTIAL AND SEC.
 R302.11 FBC-RESIDENTIAL. REVISE DETAILS AS REQUIRED AND
 PROVIDE FIREBLOCKING AT TOP OF STAIRS AS REQUIRED BY
 SEC. R302.11(3) FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 4- SHEET A-2:
 LOW SLOPE ROOFS: PROVIDE DETAILS AND SPECIFICATIONS FOR
 OVERFLOW DRAINS AND SCUPPERS AS REQUIRED BY SEC.
 R903.4.1 FBC-RESIDENTIAL.
 PROVIDE DETAILS AND SPECIFY LOCATION ON ROOF.
  
 RESPONSE:
 NEED TO SPECIFY THE OVERFLOW SCUPPERS COMPLYING WITH
 R903.4.1 FBC-RESIDENTIAL. OVERFLOW SCUPPERS ARE LOCATED
 NOT LESS THAN2" ABOVE THE FINISH ROOF.
 NOTE: OVERFLOW SCUPPERS ARE ADDITIONAL TO THE REGULAR
 SCUPPERS LOCATED AT THE LOWEST POINT OF THE ROOF.
  
 ORIGINAL COMMENT:
 5- PARAPET WALL DETAILS: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR ATTACHMENT OF 2X8 WOOD-NAILER AND
 WALL COPING. STRUCTURAL DETAILS DON'T PROVIDE THIS
 INFORMATION.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS ON SHEET A-2 STILL DON'T SPECIFY FASTENING OF
 2X P.T. WOOD NAILER TO TOP OF WALL.
  
 ORIGINAL COMMENT:
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)ALL WINDOWS AS SPECIFIED ON PLANS.
 B)ALL EXTERIOR DOORS AS SPECIFIED ON PLANS.
 C)ENTRY DOOR.
 D)OVERHEAD GARAGE DOOR.
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 F) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NO RESPONSE ON THIS ITEM. DEFERRED SUBMITTAL: PRODUCT
 APPROVALS CAN BE SUBMITTED LATER AFTER THE PERMIT IS
 ISSUED.
  
 ORIGINAL COMMENT:
 7- PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING
 SPECIFICATIONS FOR:
 A) OK.
  
 B) EXTERIOR DOORS.
  
 RESPONSE:
 2X4 STRUCTURAL BUCK SPECIFIED ON DETAIL 8/A-2.1 ON
 SHEET A-2 DOESN'T PROVIDE DOOR FRAME FULL SUPPORT AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 8- A SEPARATE PERMIT APPLICATION IS REQUIRED FOR EACH
 INDEPENDENT STRUCTURE. THIS IS TO FACILITATE
 INSPECTIONS AND RECORDS RETENTION. PROVIDE A SEPARATE
 PERMIT APPLICATION FOR THE REAR STRUCTURE. SAME PLANS
 CAN BE USED. NO NEED TO SUBMIT SEPARATE PLANS. JUST ADD
 THE PERMIT APPLICATION.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT DONE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,