Plan Review Notes
Plan Review Notes For Permit 21050545
Permit Number 21050545
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-10 07:54:191ST REVIEW FBC-2020 RES.
 PERMIT- 21050545
 6/9/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A2: REFER TO SECTION 903.4.1 & 903.4.2 FBC RES
 AND SHOW OVERFLOW SCUPPER LOCATIONS. PROVIDE SIZING
 CALCULATIONS FOR BOTH THE PRIMARY AND THE OVERFLOW
 SCUPPERS, AND PROVIDE CONSTRUCTION DETAILS. REFER TO
 SECTIONS 1106.1- 1108.3 FBC P FOR FURTHER REQUIREMENTS.
  
 2) P1: CLEANOUTS ARE REQUIRED AT THE JUNCTIONS OF THE
 BUILDING DRAINS AND SEWER LINE AND SHALL BE LOCATED AT
 THE JUNCTIONS OR A MAXIMUM OF 10 FT. DEVELOPED LENGTH
 OF PIPING UPSTREAM OF THE JUNCTIONS- SECTION- P3005.2.3
 FBC RES. PLEASE NOTE THE DEFINITION OF BUILDING DRAIN:
 THE LOWEST PIPING THAT COLLECTS THE DISCHARGE FROM ALL
 OTHER DRAINAGE PIPING INSIDE THE HOUSE AND EXTENDS 30
 INCHES IN DEVELOPED LENGTH OF PIPE, BEYOND THE EXTERIOR
 WALLS AND CONVEYS THE DRAINAGE TO THE BUILDING SEWER.
  
 3) P1: PROVIDE A VENT FOR THE LAVATORY SINK SHOWN AT
 THE UPSTREAM LOCATION IN THE ISOMETRIC DRAWING- SECTION
 P3101.2.1 FBC P.
  
 4) P1: THE PLUMBING FLOOR PLAN SHOWS A 2-INCH FIXTURE
 BRANCH FOR THE WASHING MACHINE HOWEVER A 3-INCH PIPE IS
 REQUIRED PER SECTION 406.2 FBC P. (THE ISOMETRIC
 DRAWING APPEARS TO SHOW A 3-INCH).
  
 5) P2: THE EXPANSION TANK FOR THE WATER HEATER LOCATED
 UPSTREAM OF THE CHECK VALVE APPEARS TO BE IN AN
 INCORRECT LOCATION. PLEASE LOCATE THE TANK IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 GUIDELINES- SECTIONS P2801.3 & M2005.1 FBC RES.
  
 6) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC. PLEASE
 NOTE THAT THE EPL DISPLAY CARD DOES NOT PROVIDE A
 RATING FOR THE WATER HEATER, ANC COMPLETE ENERGY
 CALCULATIONS HAVE NOT BEEN SUBMITTED- SECTION R101.5
 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  