| Date |
Text |
| 2021-06-10 07:54:19 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21050545 |
| | 6/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A2: REFER TO SECTION 903.4.1 & 903.4.2 FBC RES |
| | AND SHOW OVERFLOW SCUPPER LOCATIONS. PROVIDE SIZING |
| | CALCULATIONS FOR BOTH THE PRIMARY AND THE OVERFLOW |
| | SCUPPERS, AND PROVIDE CONSTRUCTION DETAILS. REFER TO |
| | SECTIONS 1106.1- 1108.3 FBC P FOR FURTHER REQUIREMENTS. |
| | |
| | 2) P1: CLEANOUTS ARE REQUIRED AT THE JUNCTIONS OF THE |
| | BUILDING DRAINS AND SEWER LINE AND SHALL BE LOCATED AT |
| | THE JUNCTIONS OR A MAXIMUM OF 10 FT. DEVELOPED LENGTH |
| | OF PIPING UPSTREAM OF THE JUNCTIONS- SECTION- P3005.2.3 |
| | FBC RES. PLEASE NOTE THE DEFINITION OF BUILDING DRAIN: |
| | THE LOWEST PIPING THAT COLLECTS THE DISCHARGE FROM ALL |
| | OTHER DRAINAGE PIPING INSIDE THE HOUSE AND EXTENDS 30 |
| | INCHES IN DEVELOPED LENGTH OF PIPE, BEYOND THE EXTERIOR |
| | WALLS AND CONVEYS THE DRAINAGE TO THE BUILDING SEWER. |
| | |
| | 3) P1: PROVIDE A VENT FOR THE LAVATORY SINK SHOWN AT |
| | THE UPSTREAM LOCATION IN THE ISOMETRIC DRAWING- SECTION |
| | P3101.2.1 FBC P. |
| | |
| | 4) P1: THE PLUMBING FLOOR PLAN SHOWS A 2-INCH FIXTURE |
| | BRANCH FOR THE WASHING MACHINE HOWEVER A 3-INCH PIPE IS |
| | REQUIRED PER SECTION 406.2 FBC P. (THE ISOMETRIC |
| | DRAWING APPEARS TO SHOW A 3-INCH). |
| | |
| | 5) P2: THE EXPANSION TANK FOR THE WATER HEATER LOCATED |
| | UPSTREAM OF THE CHECK VALVE APPEARS TO BE IN AN |
| | INCORRECT LOCATION. PLEASE LOCATE THE TANK IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| | GUIDELINES- SECTIONS P2801.3 & M2005.1 FBC RES. |
| | |
| | 6) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC. PLEASE |
| | NOTE THAT THE EPL DISPLAY CARD DOES NOT PROVIDE A |
| | RATING FOR THE WATER HEATER, ANC COMPLETE ENERGY |
| | CALCULATIONS HAVE NOT BEEN SUBMITTED- SECTION R101.5 |
| | FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |