2021-06-04 13:25:391ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050545
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE MECHANICAL DRAWING
 INCLUDING ALL DUCT WORK, SIZES OF DUCTWORK, RETURN AIR
 PATH FROM ALL ROOMS BACK TO THE AHU, DRYER DUCT
 TERMINATION LOCATION, CONDENSATION TERMINATION
 LOCATIONS. PLEASE ALSO PROVIDE DETAILS OF RANGE AND IF
 A HOOD IS INSTALLED OVER IT. IF A HOOD IS INSTALLED IS
 IT EXHAUSTED TO THE OUTDOORS? FBC 107.2.1
  
 2) PLEASE PROVIDE INFORMATION FOR THE BBQ ON THE PATIO,
 DO THE INSTRUCTIONS REQUIRE A HOOD BECAUSE THE BBQ IS
 UNDER THE PATIO STRUCTURE?
  
 3) IS THE GARAGE/STORAGE OPEN TO THE SECOND FLOOR
 SLEEPING? HOW IS THIS ENERGY EFFICIENT?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  