| Plan Review Notes For Permit 21050545 |
| Permit Number |
21050545 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-04 09:17:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER HAS 3 #6 AND A #10 TO PANEL A? | | | | | | LOAD CALCULATION TO INCLUDE AC OR HEAT, 5KW FOR DRYER, | | | 1.5KW LAUNDRY CKT REQUIRED PER 220 NEC | | | | | | KITCHEN COUNTER OUTLETS NEED TO BE CHECKED FOR CORRECT | | | NUMBER OF REQUIRED OUTLETS. | | | | | | INTERSYSTEM BONDING STRIP PER 250.94 REQUIRED. | | | | | | SMOKE ALARM REQUIRE ON DIRST FLOOR LEADING UP TO SECOND | | | FLOOR ROOM. | | | | | | GENERAL OUTLET SPACING NOT MEETING THE REQUIREMENTS OF | | | 210.52 (MSTR BD RM, LIVING RM, DINING RM, SITTING AREA, | | | KITCHEN COUNTER) |
|