2021-06-04 09:17:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER HAS 3 #6 AND A #10 TO PANEL A?
  
 LOAD CALCULATION TO INCLUDE AC OR HEAT, 5KW FOR DRYER,
 1.5KW LAUNDRY CKT REQUIRED PER 220 NEC
  
 KITCHEN COUNTER OUTLETS NEED TO BE CHECKED FOR CORRECT
 NUMBER OF REQUIRED OUTLETS.
  
 INTERSYSTEM BONDING STRIP PER 250.94 REQUIRED.
  
 SMOKE ALARM REQUIRE ON DIRST FLOOR LEADING UP TO SECOND
 FLOOR ROOM.
  
 GENERAL OUTLET SPACING NOT MEETING THE REQUIREMENTS OF
 210.52 (MSTR BD RM, LIVING RM, DINING RM, SITTING AREA,
 KITCHEN COUNTER)