| Plan Review Notes For Permit 21050536 |
| Permit Number |
21050536 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-24 07:59:59 | REPLACE DOORS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED = | | | 1) PLEASE SHOW THE WIND DESIGN PRESSURES FOR THE | | | OPENINGS FBC 1609.1.1 | | | 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR DESIGN FBC | | | 1603.1.4 | | | 3) PRODUCT APPROVAL (15-0826.23) HAS EXPIRED - PLEASE | | | PROVIDE AN UPDATED VERSION. | | | | | | |
|