Plan Review Notes
Plan Review Notes For Permit 21050516
Permit Number 21050516
Review Stop G
Sequence Number 1
Notes
Date Text
2021-05-19 12:02:131ST REVIEW FBC-2020 RES.
 PERMIT-21050516
 5/19/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER SHOWS AN UPGRADED 2-PSI METER, HOWEVER
 NO REGULATORS HAVE BEEN ADDED FOR THE POOL HEATER AND
 INTERIOR APPLIANCES WHICH EACH HAVE LOW PRESSURE
 INPUTS. PLEASE SHOW REQUIRED REGULATORS AND ADD THE
 COST OF THE WORK TO THE TOTAL VALUE OF THE PROJECT-
 SECTIONS G2421.2 FBC RES AND 109.3 WPB.
  
 2) THE SURVEY INCORRECTLY INDICATES A 5 FT. CLEARANCE
 FROM THE GENERATOR TO WINDOW AND DOOR OPENINGS AND
 VENTS HOWEVER A 10 FT. CLEARANCE IS REQUIRED- SECTION
 R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
2021-05-19 07:47:08 
 1ST REVIEW FBC-2020 RES.
 PERMIT-21050516
 5/19/2021
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) THE GAS RISER SHOWS AN UPGRADED 2-PSI METER, HOWEVER
 NO REGULATORS HAVE BEEN ADDED FOR THE POOL HEATER AND
 INTERIOR APPLIANCES WHICH EACH HAVE LOW PRESSURE
 INPUTS. PLEASE SHOW REQUIRED REGULATORS AND ADD THE
 COST OF THE WORK TO THE TOTAL VALUE OF THE PROJECT-
 SECTIONS G2421.2 FBC RES AND 109.3 WPB.
 2) THE SURVEY INCORRECTLY INDICATES A 5 FT. CLEARANCE
 FROM THE GENERATOR TO WINDOW AND DOOR OPENINGS AND
 VENTS HOWEVER A 10 FT. CLEARANCE IS REQUIRED- SECTION
 R303.5.1 FBC RES.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  