| 2021-05-19 12:02:13 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT-21050516 |
| | 5/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS RISER SHOWS AN UPGRADED 2-PSI METER, HOWEVER |
| | NO REGULATORS HAVE BEEN ADDED FOR THE POOL HEATER AND |
| | INTERIOR APPLIANCES WHICH EACH HAVE LOW PRESSURE |
| | INPUTS. PLEASE SHOW REQUIRED REGULATORS AND ADD THE |
| | COST OF THE WORK TO THE TOTAL VALUE OF THE PROJECT- |
| | SECTIONS G2421.2 FBC RES AND 109.3 WPB. |
| | |
| | 2) THE SURVEY INCORRECTLY INDICATES A 5 FT. CLEARANCE |
| | FROM THE GENERATOR TO WINDOW AND DOOR OPENINGS AND |
| | VENTS HOWEVER A 10 FT. CLEARANCE IS REQUIRED- SECTION |
| | R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| 2021-05-19 07:47:08 | |
| | 1ST REVIEW FBC-2020 RES. |
| | PERMIT-21050516 |
| | 5/19/2021 |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) THE GAS RISER SHOWS AN UPGRADED 2-PSI METER, HOWEVER |
| | NO REGULATORS HAVE BEEN ADDED FOR THE POOL HEATER AND |
| | INTERIOR APPLIANCES WHICH EACH HAVE LOW PRESSURE |
| | INPUTS. PLEASE SHOW REQUIRED REGULATORS AND ADD THE |
| | COST OF THE WORK TO THE TOTAL VALUE OF THE PROJECT- |
| | SECTIONS G2421.2 FBC RES AND 109.3 WPB. |
| | 2) THE SURVEY INCORRECTLY INDICATES A 5 FT. CLEARANCE |
| | FROM THE GENERATOR TO WINDOW AND DOOR OPENINGS AND |
| | VENTS HOWEVER A 10 FT. CLEARANCE IS REQUIRED- SECTION |
| | R303.5.1 FBC RES. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |