2021-06-01 15:00:1506/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR SANITARY AND WATER PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 2. SUBMIT FIRE STOPPING DETAILS FOR ANY NEW PLUMBING
 PENETRATIONS THAT WILL BE MADE THROUGH THE EXISTING
 SLAB PER THE WPB AMENDMENTS TO FBC SEC. 107.3.5.1.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  