| Date |
Text |
| 2021-06-03 17:12:30 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21050468 |
| | ADD: 1100 S. FLAGLER DR. # 1702 |
| | CONT: ED?S ISLAND TIME SERVICES, INC. |
| | TEL: 561-541-0004 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 03RD/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE INTERIOR DEMO PLAN THERE WERE NO NOTES ABOUT |
| | FLOOR FINISHES BEING REMOVED. SHEET A1 THE PROPOSED |
| | FLOOR PLAN |
| | NOTE # 12 INDICATES PROVIDE IMPACT INSULATION/ |
| | UNDERLAYMENT AT NEW FINISHES (50 IIC) MIN) PER FBC. |
| | CHAPTER 12. THE PROPOSED FLOOR PLAN DOES NOT INDICATE |
| | ANY FLOOR FINISHES BEING REMOVED AND REPLACED. |
| | FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE, |
| | VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A ( THIS BUILDING ONLY 8 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. |
| | |
| | 2A) PLEASE BE AWARE THIS BUILDING WAS DESIGNED AND |
| | BUILT UNDER THE FAIR HOUSING GUIDELINES. SECTION 3 FAIR |
| | HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENT. FOR |
| | THE PURPOSE OF THIS SECTION, A COVERED MULTIFAMILY |
| | DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED |
| | FOR THE FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991. |
| | THE INTERIOR DOORS WIC# 2 & WIC# 4 BOTH ARE LABELED AS |
| | 2680 OR 2 FEET 6 INCHES IN WIDTH OR 30-INCH-WIDE DOORS. |
| | PLEASE REVIEW REQUIREMENT # 3 USEABLE DOORS (INTERIOR |
| | DOORS) CLOSETS LESS THAN 24 INCHES IN DEPTH ARE NOT |
| | CONSIDERED USEABLE DOORS. WHERE THIS CODE SECTION (FAIR |
| | HOUSING) REQUIRES A MINIMUM CLEAR WIDTH OF 32 INCHES, |
| | THE ACTUAL DOOR MINIMUM IS A 32 INCH WIDE DOOR THEY DO |
| | NOT WORRY ABOUT THE DOOR STOP. THE MINIMUM SIZE OF A |
| | SWING DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY |
| | WITH THE SWINGING DOORS SHALL BE MEASURED BETWEEN THE |
| | FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| | DEGREES. |
| | |
| | 2B) AS AN ALTERNATE TO THE DESIGN. FAIR HOUSING |
| | GUIDELINES. FAIR HOUSING ACT DESIGN AND CONSTRUCTION |
| | REQUIREMENTS. FOR PURPOSES OF THIS SECTION, A COVERED |
| | MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND |
| | CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, |
| | 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST |
| | BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED |
| | MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR |
| | LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990. |
| | FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER: |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED WALK IN CLOSET DESIGN FOR CLOSETS 2 & 4 DOES |
| | NOT MEET THE REQUIREMENTS OF THE FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES. THE OWNER AGREES TO REVERT |
| | THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF SO |
| | REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |