2021-05-25 06:34:16PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 OFFICE AREA ACCORDING TO FBC M 403.3.1.1 AND TABLE
 403.3.1.1 NOT THE ARCHICT'S OCCUPANT LOAD FOR THE
 SPACE. OUTDOOR AIR REQUIRED IS 296 CFM.
  