Plan Review Notes
Plan Review Notes For Permit 21050388
Permit Number 21050388
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-01 15:00:321ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21050388
 6/1/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: THE CONDENSATE FROM THE REFRIGERATION
 SYSTEMS SHALL NOT DRAIN INTO THE SANITARY SYSTEM IN
 ACCORDANCE WITH SEC. 90-126 CITY OF WEST PALM BEACH
 CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED PLACE OF
 DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SECTION
 314.2.1 FBC P.
  
 2) P2.1: PLEASE UPDATE THE PLAN TO SHOW A NEW GREASE
 INTERCEPTOR WILL BE INSTALLED BASED ON THE SUBMITTED
 PERMIT APPLICATION 21050463 FOR A NEW GREASE
 INTERCEPTOR- SECTION 105.1 & 107.2.1 WPB. PLEASE SHOW
 THE LOCATION OF THE GREASE INTERCEPTOR SAMPLING PORT ON
 THE PLAN- SECTION 1003.3.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  