Plan Review Notes
Plan Review Notes For Permit 21050388
Permit Number 21050388
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-20 11:46:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21050388
 W. P. B. PERMIT: 20010941
 ADD: 5300 45TH ST.
 CONT: CREIGHTON CONSTRUCTION & TBD / TO BE DETERMINED
 TEL: 239-284-7954
 E-MAIL: [email protected]
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 20TH/ 2021
 ACTION: DENIED
  
 1) COMMENT FROM 1ST REVIEW. SHEET A0.1 CODE COMPLIANCE
 INFORMATION SHEET AND SHEET A1.5 THE EGRESS PLAN BOTH
 SHOW MERCANTILE AND THE SALES AREAS WITHIN THE TENANT
 SPACE TAKING THE OCCUPANT LOAD FACTOR @ 30 SQ. FEET PER
 OCCUPANT. SHEET A0.1 DOES NOT STATE YOU ARE TAKING A
 INCREASED OCCUPANT LOAD PER SECTION 1004.2. THE PLANS
 STATE THE OCCUPANT LOAD IS TAKEN FROM TABLE 1004.1.2 OF
 THE 2017 FBC-B.
 2) SHEET A1.1 IS LABELED ACCESSIBILITY NOTE WHEREAS
 THEY ARE ACTUALLY GENERAL ASSOCIATED NOTES. DISCREPANCY
 IN PLAN NOTATION. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
 3) SHEET A1.3 THE DETAIL # 2 HAS REVERTED BACK TO THE
 SINGLE LINE STRIPING OF PARKING SPACES, DOES NOT MEET
 THE W. P. B. MUNI CODE. 2017 ACCESSIBILITY CODE SECTION
 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT
 LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE
 WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE
 COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
 4) SHEET A1.3 NOTES 43 & 44 REVISION # 6 INDICATES A
 NEW LANDING AND RAMP BUT THERE IS NO MENTION OF EITHER
 A HANDRAIL OR EDGE PROTECTION IN COMPLIANCE WITH THE
 2017 ACCESS. CODE SECTIONS 405.8 OR 405.9.
 5A) SHEET A2.4 CONDENSING UNIT STANDS. PRODUCT APPROVAL
 IS REQUIRED. BUILDING PROVISO/ DEFERRED SUBMITTAL. 2017
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS.
 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 6) SHEET A5.0 THE CABINETRY AT THE POINT OF SALE IS NOT
 DIMENSIONED FROM FINISH FLOOR TO THE TOP OF THE
 COUNTER. 2017 FBC-ACCESSIBILITY CODE SECTION:
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 2017 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  