| Plan Review Notes For Permit 21050364 |
| Permit Number |
21050364 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-02 09:32:08 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21050364 | | | 6/2/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1: THE PLUMBING SYSTEMS FOR THE PROPOSED | | | PROJECT SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE | | | WITH THE FBC- 2020 7TH EDITION RESIDENTIAL CODE. PLEASE | | | REVISE THE INCORRECT COMPLIANCE DATA AND CODE SECTIONS | | | SPECIFIED IN THE NOTES- SECTION 107.2.1 WPB. | | | | | | 2) P1: UNDER NOTE #17 PLEASE INCLUDE THE COMPLIANCE AND | | | CONFORMANCE DATA FOR THE BATH TUB VALVE- SEE SECTION | | | P2713.3 FBC RES. | | | | | | 3) P1.1: PLEASE ADD THE SLOPE OF THE FINISHED SHOWER | | | FLOOR TO THE DETAIL- 1/4 UNIT VERTICAL IN 12 UNITS | | | HORIZONTAL (2-PERCENT SLOPE) NOR MORE THAN 1/2 UNIT | | | VERTICAL PER 12 UNITS HORIZONTAL (4-PERCENT SLOPE)- | | | SECTION P2709.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|