| 2021-06-02 10:14:27 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21050364 |
| | 6/2/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2.0: SHEET P1: THE GAS PIPING AND APPLIANCE |
| | INSTALLATIONS FOR THE PROPOSED PROJECT SHALL BE |
| | DESIGNED AND INSTALLED IN ACCORDANCE WITH THE FBC- 2020 |
| | 7TH EDITION RESIDENTIAL CODE. PLEASE REVISE THE |
| | INCORRECT COMPLIANCE DATA AND CODE SECTIONS SPECIFIED |
| | IN THE NOTES- SECTION 107.2.1 WPB. |
| | |
| | 2) P2.0: CORRECT THE NOTE ON THE RISER INDICATING PE |
| | PIPING ON THE INSIDE AND CAST IRON ON THE OUTSIDE. PE |
| | PIPE IS FOR OUTDOOR UNDERGROUND USE ONLY- SECTION |
| | G2415.17.1, AND CAST IRON IS NOT AN APPROVED GAS PIPING |
| | MATERIAL- SECTION G2414.4.1 FBC RES. |
| | |
| | 3) P2.0: FBC RES. FUEL GAS CHAPTER 24 AND SECTION |
| | 107.3.5.3 - PROVIDE A COMPLETE CODE COMPLIANT RISER |
| | DRAWING WITH THE FOLLOWING INFORMATION: |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | C) TYPES AND SIZES OF PIPING. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS, |
| | AND PIPE UNIONS. |
| | G) OUTLET PRESSURES AT REGULATORS. |
| | H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | I) PIPE SIZING TABLES. |
| | |
| | 4) P2.0 GAS WATER HEATER: PLACE A NOTE INDICATING NEW |
| | OR EXISTING VENT SYSTEM. IF A NEW SYSTEM IS TO BE |
| | INSTALLED, PLEASE REFER TO SECTIONS G2427.1 & G2448.1 |
| | FBC RES AND PROVIDE A DIAGRAM AND SPECIFICATIONS. |
| | |
| | 5) P2.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- REFER |
| | TO SECTION G2407.1 FBC RES. |
| | |
| | 6) P2.0: BASED ON THE INSTALLATION MANUAL FOR THE NEW |
| | ARTISAN BBQ GRILL, THE UNIT SHALL NOT BE INSTALLED |
| | UNDER OVERHEAD COMBUSTIBLE CONSTRUCTION OR IN AN |
| | ENCLOSED AREA. PLEASE SEE PAGES 5 & 6 OF THE MANUAL AND |
| | SHOW COMPLIANCE- SECTION G2408.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |