Plan Review Notes
Plan Review Notes For Permit 21050364
Permit Number 21050364
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-02 10:14:271ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21050364
 6/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2.0: SHEET P1: THE GAS PIPING AND APPLIANCE
 INSTALLATIONS FOR THE PROPOSED PROJECT SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE FBC- 2020
 7TH EDITION RESIDENTIAL CODE. PLEASE REVISE THE
 INCORRECT COMPLIANCE DATA AND CODE SECTIONS SPECIFIED
 IN THE NOTES- SECTION 107.2.1 WPB.
  
 2) P2.0: CORRECT THE NOTE ON THE RISER INDICATING PE
 PIPING ON THE INSIDE AND CAST IRON ON THE OUTSIDE. PE
 PIPE IS FOR OUTDOOR UNDERGROUND USE ONLY- SECTION
 G2415.17.1, AND CAST IRON IS NOT AN APPROVED GAS PIPING
 MATERIAL- SECTION G2414.4.1 FBC RES.
  
 3) P2.0: FBC RES. FUEL GAS CHAPTER 24 AND SECTION
 107.3.5.3 - PROVIDE A COMPLETE CODE COMPLIANT RISER
 DRAWING WITH THE FOLLOWING INFORMATION:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS,
 AND PIPE UNIONS.
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 4) P2.0 GAS WATER HEATER: PLACE A NOTE INDICATING NEW
 OR EXISTING VENT SYSTEM. IF A NEW SYSTEM IS TO BE
 INSTALLED, PLEASE REFER TO SECTIONS G2427.1 & G2448.1
 FBC RES AND PROVIDE A DIAGRAM AND SPECIFICATIONS.
  
 5) P2.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- REFER
 TO SECTION G2407.1 FBC RES.
  
 6) P2.0: BASED ON THE INSTALLATION MANUAL FOR THE NEW
 ARTISAN BBQ GRILL, THE UNIT SHALL NOT BE INSTALLED
 UNDER OVERHEAD COMBUSTIBLE CONSTRUCTION OR IN AN
 ENCLOSED AREA. PLEASE SEE PAGES 5 & 6 OF THE MANUAL AND
 SHOW COMPLIANCE- SECTION G2408.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  