| Plan Review Notes For Permit 21050325 |
| Permit Number |
21050325 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-21 14:11:01 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | | | 1) PERMIT APPLICATION MENTIONS THAT A VENT DRYER AND | | | RANGE HOOD ARE ALSO BEING INSTALLED. PLEASE SHOW | | | ELECTRICAL FOR NEW RANGE HOOD. | | | | | | 2) LAUNDRY ROOM REQUIRES A GFCI RECEPTACLE IN ADDITION | | | TO DEDICATED CIRCUITS FOR WASHER AND DRYER. PLEASE | | | INDICATE IF EXISTING OR INCLUDE IF NEW. | | | | | | 3) DRAWINGS NEED TO HAVE SIGNATURE, NAME, AND LIC | | | NUMBER OF CONTRACTOR QUALIFIER. | | | | | | | | | ENRIQUE QUINONEZ PE | | | ELECTRICAL PLANS EXAMINER | | | DEVELOPMENT SERVICES | | | CITY OF WEST PAM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6746. | | | |
|