| 2021-10-21 15:50:37 | 10/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. DONE. |
| | |
| | 2. DONE. |
| | |
| | 3. DONE. |
| | |
| | 4. DONE. |
| | |
| | 5. DONE AND NEW COMMENTS ON PAGE A 501; |
| | |
| | A. THE DETAIL A ON THE TOILET GRAB BAR SAYS 6 INCHES |
| | FROM THE WALL, WHICH IS NOT AN ACTUAL NUMBER AS THE |
| | TOILET IS 16 INCHES TO 18 INCHES TO THE CENTER, AND |
| | THAT NUMBER MAY CONFUSE THE INSTALLER. WOULD YOU PLEASE |
| | CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL THREE, THE BOTTOM ON THE LAV SHALL BE A |
| | MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE 2020 FBC |
| | SEC. 306.3. |
| | |
| | 6. DONE. |
| | |
| | 7. DONE. |
| | |
| | 8. DONE. |
| | |
| | 9. DONE. |
| | |
| | 10. DONE. |
| | |
| | 11. DONE. |
| | |
| | 12. NEW COMMENT, ON SHEET P2.1.1, SHOWS HOT WATER LINES |
| | UNDERGROUND AND NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. |
| | |
| | 13. NEW COMMENT, |
| | |
| | |
| | A. ON SHEETS P4.11, IT SHOWS THE MOP SINK GOING INTO |
| | THE SANITARY, AND IT SHOULD GO INTO THE GREASE |
| | INTERCEPTOR. |
| | |
| | B. WOULD YOU PLEASE SHOW A TRAP PRIMER PER THE 2020 FBC |
| | SEC. 1002.4.1 TRAP SEAL PROTECTION. |
| | |
| | 14. NEW COMMENT ON SHEET P4.1.2; |
| | |
| | A. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER |
| | ARRESTORS FOR ALL QUICK CLOSING VALVES PER THE 2020 FBC |
| | SEC. P 604.9. |
| | |
| | B. WOULD YOU PLEASE SHOW THE MAIN SHUTOFF VALVE PERT |
| | THE 2020 FBC SEC. P 606.1. |
| | |
| | C. WOULD YOU PLEASE NOTE NEXT TO THE WATER HEATER |
| | REEFING TO THE DETAIL ON PAGE P5.1.1 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |