Plan Review Notes
Plan Review Notes For Permit 21050305
Permit Number 21050305
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-16 06:44:231) SHT. ALS 1.2 - CODE DATA TABLE - THE 202 FLORIDA
 BUILDING CODE IS IN EFFECT, NOT THE 2017. REVISE THE
 CODES.
 2) SHT. ALS 1.2 - PLUMBING FIXTURE CALCULATIONS TABLE -
 THE NUMBER OF FIXTURES SHOWN IN THE TABLE DO NOT MATCH
 THE NUMBER OF FIXTURES SHOWN ON THE FLOOR PLAN. WHERE
 ARE THE OTHER FIXTURES LOCATED?
 3) A NOTE AT THE BOTTOM OF THE FIXTURE CALCULATION
 TABLE STATES "1 UNISEX STAFF RESTROOM PROVIDED IN
 TENANT SPACE." WHERE IS THIS RESTROOM?
 4) SHOW THE LOCATION AND SIZE OF THE GREASE
 INTERCEPTOR. SUBMIT SIZING CALCUALTIONS FOR THE
 INTERCEPTOR TO ENSURE PROPER CAPACITY PER FBC-PLUMBING
 SEC. 1003.2.
 5) PROVIDE A WALL FINISH SCHEDULE FOR THE TOILET ROOMS
 AND FOR THE WALLS AROUND THE SERVICE SINK. WALL FFINISH
 SHALL COMPLY WITH FBC-BUILDDING SEC.1210.2.2.
 6) SHT. A 5.0.1 - DETAILS "A" & "B" - THE GRAB BAR
 ADJACENT TO THE WATER CLOSET IS SHOWN AS BEING 6 INCHES
 FROM THE REAR WALL. THIS GRAB BAR IS REQUIRED TO EXTEND
 A MINIMUM OF 54 INCHE FROM THE REAR WALL. REFER TO
 FBC-ACCESS. SEC.604.5.1 AND FIGURE 604.5.1.THE MOUNTING
 HEIGHT DETAILS SHOW 12 INCHES.
 7) SHT. GI.0.1 - SHEET INDEX - THERE ARE SHEETS LISTED
 IN THE INDEX THAT ARE NOT PART OF THIS SUBMITTAL.
 CLARIFY.
 8) SHT. P.0.0 - NOTE #33 - THE REFERENCED ASSE 1022
 BACKFLOW DEVICE IS FOR CARBONATED BEVERAGE DISPENSERS.
 BACKFLOW DEVICES FOR COFFEE AND NON-CARBONATED BEVERAGE
 DISPENSERS IS ASSE 1024.
 9) THE WATER FILTER SYSTEM SHALL BE EQUIPPED WITH A
 BACKFLOW PREVENNTER. FBC-PLUMBING SEC.608..4.
 10) SHT.P4.11 - IDENTIFY ALL FIXTURES/EQUIPMENT ON THE
 WATER RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SHT.P4.11 - SUBMIT AN EXPANDED WATER RISER FOR
 REVIEW. IT IS EXTREMELY DIFFICULT TO DETERMINE WHERE
 HOT AND COLD WATER LINES ARE CONNECTED. WPB AMEND. TO
 FBC SEC. 107.2.1.
 12) SUBMIT DETAILS ON THE WATER HEATER STAND AND HOW IT
 WILL BE FASTENED TO THE WALL. WPB AMEND. TO FBC SEC.
 107.2.1.
 13) THE HOT WATER SYSTEM AND RECIRCULATION SYSTEM SHALL
 BE INSULATED WITH A MINIMUM OF 1 INCH THICK INSULATION
 AND SHALL BE INSULATED IN ACCORDANCE WWITH TABLE
 C403.2.10 OF THE FBC-ENERGY DEPENDING ON THE PIPE SIZE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  