| 2021-07-16 06:44:23 | 1) SHT. ALS 1.2 - CODE DATA TABLE - THE 202 FLORIDA |
| | BUILDING CODE IS IN EFFECT, NOT THE 2017. REVISE THE |
| | CODES. |
| | 2) SHT. ALS 1.2 - PLUMBING FIXTURE CALCULATIONS TABLE - |
| | THE NUMBER OF FIXTURES SHOWN IN THE TABLE DO NOT MATCH |
| | THE NUMBER OF FIXTURES SHOWN ON THE FLOOR PLAN. WHERE |
| | ARE THE OTHER FIXTURES LOCATED? |
| | 3) A NOTE AT THE BOTTOM OF THE FIXTURE CALCULATION |
| | TABLE STATES "1 UNISEX STAFF RESTROOM PROVIDED IN |
| | TENANT SPACE." WHERE IS THIS RESTROOM? |
| | 4) SHOW THE LOCATION AND SIZE OF THE GREASE |
| | INTERCEPTOR. SUBMIT SIZING CALCUALTIONS FOR THE |
| | INTERCEPTOR TO ENSURE PROPER CAPACITY PER FBC-PLUMBING |
| | SEC. 1003.2. |
| | 5) PROVIDE A WALL FINISH SCHEDULE FOR THE TOILET ROOMS |
| | AND FOR THE WALLS AROUND THE SERVICE SINK. WALL FFINISH |
| | SHALL COMPLY WITH FBC-BUILDDING SEC.1210.2.2. |
| | 6) SHT. A 5.0.1 - DETAILS "A" & "B" - THE GRAB BAR |
| | ADJACENT TO THE WATER CLOSET IS SHOWN AS BEING 6 INCHES |
| | FROM THE REAR WALL. THIS GRAB BAR IS REQUIRED TO EXTEND |
| | A MINIMUM OF 54 INCHE FROM THE REAR WALL. REFER TO |
| | FBC-ACCESS. SEC.604.5.1 AND FIGURE 604.5.1.THE MOUNTING |
| | HEIGHT DETAILS SHOW 12 INCHES. |
| | 7) SHT. GI.0.1 - SHEET INDEX - THERE ARE SHEETS LISTED |
| | IN THE INDEX THAT ARE NOT PART OF THIS SUBMITTAL. |
| | CLARIFY. |
| | 8) SHT. P.0.0 - NOTE #33 - THE REFERENCED ASSE 1022 |
| | BACKFLOW DEVICE IS FOR CARBONATED BEVERAGE DISPENSERS. |
| | BACKFLOW DEVICES FOR COFFEE AND NON-CARBONATED BEVERAGE |
| | DISPENSERS IS ASSE 1024. |
| | 9) THE WATER FILTER SYSTEM SHALL BE EQUIPPED WITH A |
| | BACKFLOW PREVENNTER. FBC-PLUMBING SEC.608..4. |
| | 10) SHT.P4.11 - IDENTIFY ALL FIXTURES/EQUIPMENT ON THE |
| | WATER RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) SHT.P4.11 - SUBMIT AN EXPANDED WATER RISER FOR |
| | REVIEW. IT IS EXTREMELY DIFFICULT TO DETERMINE WHERE |
| | HOT AND COLD WATER LINES ARE CONNECTED. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 12) SUBMIT DETAILS ON THE WATER HEATER STAND AND HOW IT |
| | WILL BE FASTENED TO THE WALL. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 13) THE HOT WATER SYSTEM AND RECIRCULATION SYSTEM SHALL |
| | BE INSULATED WITH A MINIMUM OF 1 INCH THICK INSULATION |
| | AND SHALL BE INSULATED IN ACCORDANCE WWITH TABLE |
| | C403.2.10 OF THE FBC-ENERGY DEPENDING ON THE PIPE SIZE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |