Plan Review Notes
Plan Review Notes For Permit 21050305
Permit Number 21050305
Review Stop G
Sequence Number 1
Notes
Date Text
2021-07-16 13:15:171) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 EQUIPMENT. EQUIPMENT SHALL BE LISTED AND LABELED PER
 FBC-FUEL GAS SEC. 301.3.
 2) IDENTIFY EACH APPLIANCE ON THE GAS RISER ALONG WITH
 THE BTU LOAD FOR EACH APPLIANCE. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) SIZE ALL DROPS ON HE GAS RISER AND SIZE THE GAS LOOP
 AND ALL LINES DOWNSTREAM OF THE REGULATORS.. WPB AMEND.
 TO FBC SEC. 107.2.1.
 4) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. 304.1. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3 OR
 FBCR G2407.9.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FFOR THE REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHT.FG0.0.0 - NATURAL GAS PIPE SIZING TABLE - THE
 TABLE LISTS THE 2 PSI SYSTEM AS COMPLYING WITH TABLE
 402.4 (3) OF THE FUEL GAS CODE. THIS TABLE IS FOR LESS
 THAN A 2 PSI SYSTEM. PROVIDE THE CORRECT SIZING TABLE
 FOR THE 2 PSI SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. FG0.0.0 - THE GAS SIZING TABLE ALSO REFERS TO
 THE 2017 FUEL GAS CODE. THE GAS CODE IN EFFECT IS THE
 2020 CODE. REVISE THE TABLE TO REFLECT THE 2020 CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW