2021-06-14 14:06:0106/14/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A COMPLETE EVALUATION OF ALL GAS
 EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO
 CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE. I
 HAVE RESEARCHED CITY RECORDS BACK TO 2000, AND THERE IS
 NO RECORD OF A PERMIT FOR THE INSTALLATION OF AN LP
 TANK. WHAT THIS "EXISTING" TANK SUPPLIES OTHER
 APPLIANCES/EQUIPMENT? SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN
 THIS PERMIT FOR THIS SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. DONE...PLEASE HAVE A SIGNATURE ON THE ISOMETRIC
 DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT
 ACCORDING TO FLORIDA ADMINISTRATIVE CODE 61G15-23.001,
 FLORIDA STATUTE 471 PER THE WPB AMENDMENTS FBC SEC.
 107.1 GENERAL.
  
 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, AND). IN ADDITION, SHOW ON THE
 ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 4. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR THE
 GENERATORS TO VERIFY COMPLIANCE WITH 2017 FBC FG
 SEC.305.1 OR 2017 FBC RES. SEC. G2408.1.
  
 5. SECOND REQUEST, PLEASE SUBMIT THE CORRECT BTU LOAD
 ON THE SYSTEM. THE 193 IS INCORRECT, AND IF THERE ARE
 ANY OTHER APPLIANCES CONNECTED TO THE SYSTEM, PLEASE
 PROVIDE THEM AS WELL. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 6. DONE...SHOW THE DISTANCE FROM THE POINT OF DELIVERY
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 7. SECOND REQUEST, PLEASE SHOW AND LABEL ALL UNIONS IN
 FRONT OF REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND
 SHUTOFF VALVE PER THE 2020 FBC RES. SEC G2421.2.
  
 8. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET
 FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING
 LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS PERT THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 9. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE DRIVEWAY AND ADJACENT PROPERTY LINES,
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER THE NFPA 58, TABLE 3-2.2.2. PLEASE NOTE THAT IF THE
 TANK IS LESS TANK 10 FT. FROM THE DRIVEWAY, THE SHELL
 FOR THE TANK SHALL BE 18 IN. ABOVE GRADE, AND VEHICULAR
 BARRIER PROTECTION WILL BE REQUIRED.
  
 10. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE
 TO COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 11. THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLING A CATHODIC PROTECTION SYSTEM CONSISTING
 OF A SACRIFICIAL ANODE OR AN IMPRESSED CURRENT ANODE
 PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA 58. INDICATE
 THE TYPE OF PROTECTION AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 6.17.1. SUBMIT DETAILS ON THE
 TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & THE NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT
 OF WATER TO ACTIVATE IT.
  
 12. THE ENGINEERED TIE-DOWN SUPPLIED SHEET FOR THE LP
 TANK TIE-DOWN METHOD, STRAPS, OR CABLE, AND HOW THE
 CABLE IS PROTECTED FOR THE LP TANK AND APPURTENANCES,
 DOES NOT HAVE THE CURRENT CODE YEAR AS IT SAYS 2017.
 THIS IS A SIGNED AND SEALED DOCUMENT. IT WILL REQUIRE
 THE ORIGINAL DROPPED OFF AT THE CITY OR AN ELECTRONIC
 SIGNATURE SUBMITTED PER NFPA 58 AND WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 PLEASE CONTACT ME FOR FURTHER ASSISTANT ON THIS REVIEW
 AS THE LOCATION OF THE TANK AND THE PAPERWORK SUBMITTED
 ARE UNCLEAR.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR