| 2021-05-12 12:50:21 | 05/12/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT |
| | WILL BE DONE AT THE FIELD, AND IF NOT TO CODE, IT MAY |
| | NEED TO BE BOUT UP TO CODE COMPLIANCE. I HAVE |
| | RESEARCHED CITY RECORDS BACK TO 0000, AND THERE IS NO |
| | RECORD OF A PERMIT FOR THE INSTALLATION OF AN LP TANK. |
| | WHAT THIS "EXISTING" TANK SUPPLIES OTHER |
| | APPLIANCES/EQUIPMENT? SINCE THERE IS NO RECORD OF A |
| | PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN |
| | THIS PERMIT FOR THIS SCOPE OF WORK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, |
| | ALL PIPE SIZES, AND). IN ADDITION, SHOW ON THE |
| | ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 4. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR THE GENERATORS TO VERIFY |
| | COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017 FBC RES. |
| | SEC. G2408.1. |
| | |
| | 5. PLEASE LIST THE TOTAL BTU LOAD ON THE SYSTEM. REFER |
| | TO THE 2020 FBC RES. SEC. G2413. |
| | |
| | 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF |
| | VALVE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 8. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET |
| | FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE |
| | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS |
| | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, |
| | PARKING LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS |
| | PERT THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |