Plan Review Notes
Plan Review Notes For Permit 21050270
Permit Number 21050270
Review Stop G
Sequence Number 1
Notes
Date Text
2021-05-12 12:50:2105/12/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE AT THE FIELD, AND IF NOT TO CODE, IT MAY
 NEED TO BE BOUT UP TO CODE COMPLIANCE. I HAVE
 RESEARCHED CITY RECORDS BACK TO 0000, AND THERE IS NO
 RECORD OF A PERMIT FOR THE INSTALLATION OF AN LP TANK.
 WHAT THIS "EXISTING" TANK SUPPLIES OTHER
 APPLIANCES/EQUIPMENT? SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN
 THIS PERMIT FOR THIS SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, AND). IN ADDITION, SHOW ON THE
 ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 4. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR THE GENERATORS TO VERIFY
 COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017 FBC RES.
 SEC. G2408.1.
  
 5. PLEASE LIST THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC RES. SEC. G2413.
  
 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF
 VALVE PER THE 2020 FBC RES. SEC G2421.2.
  
 8. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET
 FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS
 PERT THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  