| 2021-06-22 11:46:21 | 21050228 250 S AUSTRALIAN AVE # 1204 |
| | |
| | PLUMBING APPROVED |
| | |
| | PROVISO: |
| | |
| | 1. PLAN SHEET P0.1 AND P2.1 SHALL BE REVISED TO REFLECT |
| | THE RED-LINED COMMENTS ON THOSE PAGES AND ARE NOTED IN |
| | THIS PROVISO. THE REVISED PLANS SHALL BE SUBMITTED, |
| | APPROVED AND ON SITE PRIOR TO THE FIRST INSPECTION. |
| | ...PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION |
| | FOR SUMP PUMP DISCHARGE (PRESSURE RATED) PIPING FROM |
| | PUMP TO CONNECTION WITH SANITARY DRAINAGE |
| | ...PROVIDE FULL OPEN VALVE ON SUMP PUMP DISCHARGE PER |
| | FBC PL 712.2 |
| | ?ADD TO KEY NOTE 1, ?WHERE THE DISCHARGE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| | MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING AND SAID WYE SHALL BE LOCATED NOT LESS THAN 10 |
| | PIPE DIAMETERS FROM THE BASE OF ANY STACK OR FIXTURE |
| | DRAIN PER FBC PL 712.3.5.? |
| | |
| | 2.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED |
| | BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| | INSPECTION. |
| | |
| | 3.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED |
| | AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE |
| | PRIOR TO FINAL INSPECTION |
| | |
| | 4.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT |
| | THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY |
| | ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| | INSPECTION |
| | |
| | |
| | |
| | |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | |
| | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| | AVOID VOIDING OF THE PERMIT. |
| | |
| | |