Plan Review Notes
Plan Review Notes For Permit 21050220
Permit Number 21050220
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-27 16:10:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PLAN SHEET A1.1.1 IS TITLED FIRST FLOOR PLAN, THE
 PERMIT DESCRIPTION INDICATES THE WORK IS ON THE THIRD
 FLOOR. PER WPB FBC 107.2.1, CLARIFY.
  
 2.PER WPB FBC 107.2.1, PROVIDE THE BUILDING THIRD FLOOR
 PLAN SHOWING ACCESS TO PUBLIC TOILET ROOMS AND DRINKING
 FOUNTAIN AS REQUIRED BY FBC PL 403.3.3 AND 403.5.
  
 3.PER WPB FBC 107.2.1, PROVIDE CLEAR FLOOR OR GROUND
 SPACE FOR ACCESSIBLE SINKS TO COMPLY WITH FBC ACC 305.
  
 4.PER WPB FBC 107.2.1, PROVIDE UL ASSEMBLY FOR THIRD
 FLOOR PIPE FLOOR PENETRATIONS COMPLYING WITH FBC
 CHAPTER 7. IF THIS IS A GROUND FLOOR, PROVIDE A SLAB
 REPAIR DETAIL. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
  
 5.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 6.SANITARY RISER: THE VENT FOR LAVATORY 1 SHALL CONNECT
 ABOVE THE WEIR OF THE FIXTURE TRAP PER FBC PL 909.2 AND
 1002.3(5).
  
 7.PER FBC FL 1002.4.1, PROVIDE TRAP SEAL PROTECTION FOR
 THE FLOOR DRAIN. PER WPB FBC 107.2.1, PROVIDE A TRAP
 SEAL PROTECTION SPECIFICATION AND DETAIL COMPLYING WITH
 ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2,
 1002.4.1.3 OR 1002.4.1.4.
  
 8.THE NOTED LEONARD 170-LF-BRKT IS POINT OF USE. PER
 WPB FBC 107.2.1, DELETE THE NOTE AT THE TEMPERED AND
 COLD WATER SUPPLY CONNECTIONS FOR LAVATORY THAT ALLOWS
 ONE VALVE TO SUPPLY UP TO FIVE FIXTURES.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  