| 2021-05-27 16:10:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99-18 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.PLAN SHEET A1.1.1 IS TITLED FIRST FLOOR PLAN, THE |
| | PERMIT DESCRIPTION INDICATES THE WORK IS ON THE THIRD |
| | FLOOR. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 2.PER WPB FBC 107.2.1, PROVIDE THE BUILDING THIRD FLOOR |
| | PLAN SHOWING ACCESS TO PUBLIC TOILET ROOMS AND DRINKING |
| | FOUNTAIN AS REQUIRED BY FBC PL 403.3.3 AND 403.5. |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE CLEAR FLOOR OR GROUND |
| | SPACE FOR ACCESSIBLE SINKS TO COMPLY WITH FBC ACC 305. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE UL ASSEMBLY FOR THIRD |
| | FLOOR PIPE FLOOR PENETRATIONS COMPLYING WITH FBC |
| | CHAPTER 7. IF THIS IS A GROUND FLOOR, PROVIDE A SLAB |
| | REPAIR DETAIL. SHOW THE WIDTH OF THE REPAIR, THE |
| | MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND |
| | THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF |
| | THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE |
| | EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS |
| | AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND |
| | THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A |
| | COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A |
| | FINAL INSPECTION. |
| | |
| | 5.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 6.SANITARY RISER: THE VENT FOR LAVATORY 1 SHALL CONNECT |
| | ABOVE THE WEIR OF THE FIXTURE TRAP PER FBC PL 909.2 AND |
| | 1002.3(5). |
| | |
| | 7.PER FBC FL 1002.4.1, PROVIDE TRAP SEAL PROTECTION FOR |
| | THE FLOOR DRAIN. PER WPB FBC 107.2.1, PROVIDE A TRAP |
| | SEAL PROTECTION SPECIFICATION AND DETAIL COMPLYING WITH |
| | ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2, |
| | 1002.4.1.3 OR 1002.4.1.4. |
| | |
| | 8.THE NOTED LEONARD 170-LF-BRKT IS POINT OF USE. PER |
| | WPB FBC 107.2.1, DELETE THE NOTE AT THE TEMPERED AND |
| | COLD WATER SUPPLY CONNECTIONS FOR LAVATORY THAT ALLOWS |
| | ONE VALVE TO SUPPLY UP TO FIVE FIXTURES. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |