| Plan Review Notes For Permit 21050219 |
| Permit Number |
21050219 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-03 10:27:54 | OFFICE RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE | | | THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN EFFECT | | | (2020 FBC). | | | 2) PLEASE PROVIDE A DOOR SCHEDULE - SHOW DOOR SIZES - | | | SHOW HOURLY FIRE RATINGS. FBC 107.2.1 | | | 3) PLEASE SHOW FIRE RATED DOORS TO BE SELF LATCHING AND | | | CLOSING PER FBC 716.5.9 | | | 4) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF | | | THE ALTERATION.FBC 107.2.1 | | | 5) PLEASE SHOW THE EXISTING CORRIDOR HOURLY FIRE | | | RATING.FBC 107.2.1 | | | |
|