Plan Review Notes
Plan Review Notes For Permit 21050219
Permit Number 21050219
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-03 10:27:54OFFICE RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN EFFECT
 (2020 FBC).
 2) PLEASE PROVIDE A DOOR SCHEDULE - SHOW DOOR SIZES -
 SHOW HOURLY FIRE RATINGS. FBC 107.2.1
 3) PLEASE SHOW FIRE RATED DOORS TO BE SELF LATCHING AND
 CLOSING PER FBC 716.5.9
 4) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF
 THE ALTERATION.FBC 107.2.1
 5) PLEASE SHOW THE EXISTING CORRIDOR HOURLY FIRE
 RATING.FBC 107.2.1
  