| Plan Review Notes For Permit 21050214 |
| Permit Number |
21050214 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-16 16:17:40 | PLAN REVIEW / FUEL GAS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. SUBMIT LOW PRESSURE GAS REGULATOR SPECIFICATIONS. | | | 2020 FBC FUEL GAS SEC.305.1 OR 2020 FBC FUEL GAS RES. | | | SEC. G2408.1. | | | | | | NOTICE: REGULATORS SHALL HAVE A UNION INSTALLED WITHIN | | | 1 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2 | | | | | | NOTICE: REGULATORS SHALL BE LOCATED PER 409.1.3. | | | | | | 2. GAS PRODUCT SPECS INCLUDE ABOVE GROUND/UNDER GROUND | | | LPG TANK INSTALLATION INSTRUCTIONS. GAS RISER INDICATES | | | A NEW NG 2PSI METER WILL BE INSTALLED. | | | PLEASE CLARIFY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|