Permit Number 21050131
Review Stop M
Sequence Number 2
Notes
Date Text
2021-06-03 07:46:47THE REVISED M-3.1 VENTILATION CALCULATIONS HAVE BEEN
 ALTERED FROM THE ORIGINAL CALCULATIONS. THE REVISED
 CALCULATIONS FOR CFM'S OF OUTDOOR AIR HAVE BEEN CUT.
 THE ORIGINAL CALCULATIONS WERE CORRECT. PLEASE CHANGE
 THE REVISED CALCULATIONS BACK TO THE ORIGINAL
 CALCULATIONS (CFM'S ONLY) EXAMPLE: OFFICE SPACE WAS 150
 CFM, REVISED SHEET SHOWS 44 CFM'S.
  