| 2021-05-12 08:56:03 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21050131 |
| | 5/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.01: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS AT THE BEER AND KOMBUCHA BEVERAGE |
| | DISPENSERS- SECTION 305.1 FBC ACC. |
| | |
| | 2) A3.01: PROVIDE AN ELEVATION VIEW OF THE BEVERAGE |
| | DISPENSERS TO VERIFY COMPLIANCE WITH REQUIRED REACH |
| | RANGES- SECTIONS 904.5.1 AND 308.1 FBC ACC. |
| | |
| | 3) P1.2 & P1.3: SHUT OFF VALVES FOR INDIVIDUAL FIXTURES |
| | AND APPLIANCES NOT SHOWN- SECTION 606.2 FBC P. |
| | |
| | 4) P1.4: THE COLD-WATER BRANCH LINE SERVING THE WATER |
| | HEATER SHALL BE PROVIDED WITH A DEDICATED SHUT OFF |
| | VALVE- SECTION 503.1 FBC P. |
| | |
| | 5) P1.1: INSTALLATION OF THE NEW SINK AND HUB DRAIN MAY |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 6) THE NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACES |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |