2021-05-07 12:12:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CONFERENCE ROOM NEEDS ADDITIONAL OUTLETS PER 210.71
  
 210.71 MEETING ROOMS (B) RECEPTACLE OUTLETS REQUIRED.
 THE TOTAL NUMBER OF RECEPTACLE OUTLETS, INCLUDING FLOOR
 OUTLETS AND RECEPTACLE OUTLETS IN FIXED FURNITURE,
 SHALL NOT BE LESS THAN AS DETERMINED IN (1) AND (2).
 THESE RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 LOCATED AS DETERMINED BY THE DESIGNER OR BUILDING
 OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE
 NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH
 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE.
  
  
  