| Plan Review Notes For Permit 21050129 |
| Permit Number |
21050129 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-10 06:58:44 | 1) SHEET M-3.1: THE CONFERENCE ROOM OUTDOOR AIR | | | CALCULATION IS SHORTON CFM'S REQUIRED. PLEASE SUPPLY | | | 120 CFM'S OF OUTDOOR AIR TO THE CONFERENCE ROOM. FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | 2) NEW SHEET M-2.2: THE KEYNOTES REFERENCE 4 NOTES. | | | PLEASE SHOW THESE TRANSFER DUCTS ON THE DRAWING. FBC | | | 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|