Plan Review Notes
Plan Review Notes For Permit 21050129
Permit Number 21050129
Review Stop M
Sequence Number 2
Notes
Date Text
2021-06-10 06:58:441) SHEET M-3.1: THE CONFERENCE ROOM OUTDOOR AIR
 CALCULATION IS SHORTON CFM'S REQUIRED. PLEASE SUPPLY
 120 CFM'S OF OUTDOOR AIR TO THE CONFERENCE ROOM. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
 2) NEW SHEET M-2.2: THE KEYNOTES REFERENCE 4 NOTES.
 PLEASE SHOW THESE TRANSFER DUCTS ON THE DRAWING. FBC
 107.2.1
  