| Plan Review Notes For Permit 21050129 |
| Permit Number |
21050129 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-07 07:57:11 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONFERENCE ROOM REQUIRES MORE THAN ONE RECEPTACLE | | | OUTLET IN THE FLOOR AND ON WALLS. | | | | | | 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER | | | OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND | | | RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE | | | LESS THAN AS DETERMINED IN (1) AND (2). THESE | | | RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS | | | DETERMINED BY THE DESIGNER OR BUILDING OWNER. | | | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE | | | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH | | | 210.52(A)(1) THROUGH (A)(4). | | | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT | | | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF | | | AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE | | | NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH | | | 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE. | | | | | | | | | |
|