| 2021-06-11 17:13:31 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21050062 |
| | 6/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS. |
| | |
| | 3) FAILED. A5: PROVIDE ENLARGED SHOWER COMPARTMENT |
| | ACCESSIBILITY DETAILS: |
| | A) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.1. 18-INCH GRAB BAR LENGTH NOT SHOWN- REFER TO |
| | FIGURE 608.3.1. |
| | B) FAILED. TYPE OF SEAT, SEAT LOCATION, AND DIMENSIONS- |
| | SECTIONS 608.4. 610.3, 610.3.1, & 610.3.2. REFER TO |
| | FIGURES 610.3.1 AND 610.3.2 AND SHOW COMPLIANCE FOR |
| | SEAT DIMENSIONS AND EDGE CLEARANCES. |
| | C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.1. THE CONTROLS |
| | SHALL BE LOCATED ON THE SIDE WALL OPPOSITE OF THE SEAT. |
| | PLEASE SEE FIGURE 608.5.1 AND PROVIDE A LOCATION |
| | DIAGRAM THAT MEETS COMPLIANCE. PLEASE ADD THE SHOWER |
| | CONTROL, FAUCET, AND SPRAY TO THE FIXTURE SCHEDULE ON |
| | SHEET P4.0. |
| | |
| | 5) FAILED. A5: PROVIDE A SHOWER PAN AND CURB DETAIL IN |
| | COMPLIANCE WITH- SECTION 608.7 FBC ACC & SECTION |
| | 421.5.2 FBC P. THE DETAIL INDICATES A 3/8-INCH PER FT. |
| | SLOPE. THE MAXIMUM ALLOWABLE SLOPE IS 1/4-INCH PER FT.- |
| | SECTION 421.5.1.2. |
| | |
| | 6) FAILED. A3.0 & A5: PLEASE PROVIDE DETAILS SHOWING |
| | THE DIMENSIONS OF THE WALL TILE SURROUND FOR THE |
| | BATHROOM FIXTURES AND THE MOP SINK- SECTION 310.3 FBC P |
| | AND SECTION 1210.2.2 FBC B. NO CORRECTIONS OR WALL TILE |
| | CALLED OUT FOR BATHROOMS. |
| | |
| | NEW COMMENT. |
| | 1) SHEET A1: PLEASE SHOW THE CLEAR FLOOR SPACE FORWARD |
| | APPROACH DIAGRAMS AND DIMENSIONS AT THE ACCESSIBLE |
| | SINKS. PLEASE NOTE SECTION 212.3 SINKS FBC ACC: |
| | WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO |
| | FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |