| Plan Review Notes For Permit 21050028 |
| Permit Number |
21050028 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-17 17:38:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ARC FAULT AND GFCI ARE REQUIRED FOR ALL REPLACE AND /OR | | | NEW OUTLET CIRCCUITS. 210.8, 210.12 (B) | | | | | | SUBMIT A RISER DIAGRAM SHOWING SERVICE LOCATION AND | | | PANEL LOCATIONS IN MAIN AND ACCESSORY BUILDING 215.5 | | | | | | ACCESSORY BUILDING NEEDS A PANEL WITH A MAIN AND A | | | GROUNDING ELECTRODE SYSTEM. 250.24, 225.30, ,225,31 |
|