| Plan Review Notes For Permit 21050024 |
| Permit Number |
21050024 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-14 12:51:01 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050024 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE | | | SIGNED BY AN ENGINEER, ARCHITECT OR THE MECHANICAL | | | CONTRACTOR THAT HOLDS THE PERMIT TO DO THE PROJECT. FS | | | 471.003(H). | | | | | | 2) PLEASE SHOW THE RETURN AIR PATH FROM THE NEW LIVING | | | ROOM TO THE AHU IN THE UTILITY ROOM. FBC RES M1603.2 | | | | | | 3) PLEASE PROVIDE DETAILS FOR THE NEW RANGE AND HOOD. | | | IS THE HOOD DUCTED TO THE EXTERIOR OF THE HOME? PLEASE | | | PROVIDE THE CFM?S OF THE HOOD FAN IF IT IS DUCTED TO | | | THE EXTERIOR. FBC RES M1503.3 | | | | | | 4) PLEASE PROVIDE APPLIANCE TIE DOWN FOR THE CONDENSING | | | UNIT. FBC RES M1307.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|