| 2021-05-06 15:49:35 | FINAL ELEVATION CERTIFICATE REVIEW COMMENTS: |
| | SUBMITTAL #21041684 |
| | |
| | 1- REVISE INFORMATION ENTERED IN SECTION C2: |
| | (A) THERE IS NO INFORMATION IN THE SURVEY FOR THE |
| | ELEVATION AT THE LOADING AREA ON THE NORTH SIDE OF THE |
| | BUILDING. ACCORDING TO PLANS, THE ELEVATION AT THE |
| | ENTRANCE OF THE LOADING AREA IS LOWER THAN THE REST OF |
| | THE FLOOR. THIS LOOKS LIKE THE TOP OF BOTTOM FLOOR. |
| | REVISE AS REQUIRED. |
| | PROVIDE FINAL SURVEY SHOWING ELEVATIONS IN THE LOADING |
| | AREA. (INCLUDE THE FIRE PUMP ROOM, TRASH ROOM, DOMESTIC |
| | PUMP ROOM). |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | (B) COORDINATE WITH ITEM #1 ABOVE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | (C)OK. |
| | |
| | (D)ACCORDING TO FINAL SURVEY SUBMITTED IT LOOKS LIKE |
| | THE TOP OF ATTACHED GARAGE ELEVATION IS TAKEN AT A |
| | MIDPOINT OF THE GARAGE RAMP. THE LOWEST ELEVATION OF |
| | THE GARAGE IS AT THE ENTRANCE OF THE GARAGE. REVISE AS |
| | REQUIRED. |
| | ALSO, REVISE ELEVATION 12.4. ACCORDING TO SURVEY THIS |
| | ELEVATION IS 12.38. THE ELEVATION NEEDS TO BE ENTERED |
| | TO THE NEAREST TENTH OF A FOOT AS REQUIRED BY ITEM C2 |
| | OF FEMA ELEVATION CERTIFICATE INSTRUCTIONS. THEREFORE, |
| | THE CORRECT ROUNDING WILL BE 12.0 NOT 12.4. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | (E)OK. |
| | |
| | (F)SURVEY SUBMITTED DOESN'T SHOW THE LOWEST ADJACENT |
| | GRADE NEXT TO THE BUILDING. UNABLE TO VERIFY. PROVIDE |
| | SURVEY WITH INFORMATION. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | (G)SURVEY SUBMITTED DOESN'T SHOW THE HIGHEST ADJACENT |
| | GRADE NEXT TO THE BUILDING. UNABLE TO VERIFY. PROVIDE |
| | SURVEY WITH INFORMATION. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | (H) SURVEY SUBMITTED DOESN'T SHOW ELEVATION OF DECK OR |
| | STAIRS. UNABLE TO VERIFY. PROVIDE SURVEY WITH |
| | INFORMATION. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 2- PROVIDE PHOTOS SHOWING THE VENTS SPECIFIED ON ITEM |
| | A9(B). |
| | NOTE: COORDINATE WITH VENTS SHOWN ON SHEET A.2.1 AND |
| | DETAILS 4 AND 8 ON SHEET A-8.1.1. THERE IS A VENT |
| | INSIDE THE GARAGE CONNECTING TO THE OUTSIDE WALL. THE |
| | OTHER VENT CONSIDERED BY THE ARCHITECT OF RECORD IS THE |
| | ENTRANCE TO THE GARAGE. SHOW ALL VENTS. SEE ITEM A6 |
| | FEMA ELEVATION CERTIFICATE INSTRUCTIONS. |
| | ALSO, ALL PHOTOS NEED TO BE AT LEAST 3"X3". REVISE |
| | PHOTO THREE ON PAGE 6 OF 6. |
| | |
| | SEE ARCHITECT'S REVISION #8 ON PLANS AND REVISION |
| | #19110684 CITY RECORDS. |
| | |
| | |
| | 3- FINAL SURVEY SUBMITTED: |
| | A) PROVIDE FINAL SURVEY SHOWING ALL THE ELEVATIONS |
| | REFERENCED IN THE ELEVATION CERTIFICATE. COORDINATE |
| | WITH ITEM #1. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | B) THE POOL SHOWS A TOP OF POOL FORM-BOARD ELEVATION OF |
| | 14.49'. CLARIFY WHY IT IS A FORM-BOARD ELEVATION IF |
| | THIS IS A FINAL SURVEY. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |