| 2021-06-30 08:33:43 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE COVER SHEETS FO FL25574. |
| | |
| | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE |
| | VERSION, AND STATUS, FBC R 301. |
| | (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.) |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 2. WALL PRESSURE CALCULATOR SUBMITTED ON 6/17/21 IS |
| | BASED ON ASCE 7-10. THIS DOCUMENT HAS EXPIRED. PROVIDE |
| | DESIGN WIND LOADS PER ASCE 7-16. |
| | PROVIDE SITE SPECIFIC DESIGN WIND LOADS PER FBC CHPT 16 |
| | AND ASCE 7-16. CALCULATIONS SHALL BE PREPARED BY |
| | FLORIDA LICENSED DESIGN PROFESSIONAL. |
| | 1609.1.1DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE |
| | 7. WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| | NORMAL TO THE SURFACE CONSIDERED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |