| 2021-05-11 14:55:26 | 05/11/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P0.00; |
| | |
| | A. PLEASE ADD THE ACCESSIBILITY CODE IN THE CURRENT |
| | CYCLE UNDER APPLICABLE CODES PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. PLEASE PROVIDE DETAIL FOR THE SLAB REPAIR PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. ON SHEET P1.01; |
| | |
| | A. THE EXISTING SANITARY IS CAPPED OFF IN THE ADJACENT |
| | SIDE, AND THERE IS NO SANITARY FOR THE FUTURE TENANT IN |
| | SUITE A12. PLEASE SHOW OR GIVE AN OPTION ON HOW THE |
| | SANITARY SYSTEM WILL BE PROVIDED FOR A12 UNITS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. PLEASE SHOW A CLEAN-OUT FOR GW ENTERING THE BUILDING |
| | WITHIN TEN FEET PER THE 708.1.3 BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | 3. ON SHEET P2.00, A SEPARATE PERMIT SHALL BE OBTAINED |
| | FOR THE GREASE INTERCEPTOR; PLEASE PROVIDE A NOTE ON |
| | THIS SHEET PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 4. PLEASE PROVIDE DOCUMENTATION THAT THE EXISTING |
| | ACCESSIBILITY RESTROOM COMPLIES WITH THE CURRENT CODE |
| | OF ITS CYCLE OR GIVE A PAGE TO REFERENCE IN THE FIELD |
| | OF THE DIMENSION AND APERTURES PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |