| 2021-05-24 07:10:20 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE THE DETAILS INCLUDING THE | | | FOLLOWING: | | | | | | 1) STRUCTURAL & FIRE RATING DETAILS FOR THE INFILL OF | | | TENANT SEPARATION WALLS. | | | 2) STRUCTURAL & FIRE RATING (IF APPLICABLE) DETAILS OF | | | BATHROOM. | | | | | | |
|