| 2021-05-19 15:45:33 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | | | 1) PLEASE SHOW LOCATION OF ELECTRIC METER FBC 107 | | | | | | 2) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT | | | NEW PANELS NEC 2017 | | | | | | 3) PLEASE SPECIFY AIC RATING OF NEW PANELS NEC 2017 | | | | | | 4) PLEASE PROVIDE A RISER DIAGRAM SHOWING ELECTRIC | | | METERS, PANELS, CONDUCTOR SIZES, AND GROUNDING DETAILS | | | FBC 107, NEC 2017 | | | | | | 5) PLEASE INCLUDE NOTE INDICATING WORK TO BE DONE AS | | | PER NEC 2017 | | | | | | ENRIQUE QUINONEZ PE | | | ELECTRICAL PLANS EXAMINER | | | DEVELOPMENT SERVICES | | | CITY OF WEST PAM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6746. | | | |
|