Plan Review Notes
Plan Review Notes For Permit 21041585
Permit Number 21041585
Review Stop P
Sequence Number 4
Notes
Date Text
2021-11-30 08:37:324TH REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 11/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST, 2ND, AND 3RD REVIEWS ARE LISTED BELOW WITH
 ADDITIONAL NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED ITEMS C, E, & F- SEE BELOW.
  
 C) FAILED. SHOW THE WIDTH OF THE NEW COMPARTMENT DOORS-
 SECTION 404.2.3 FBC ACC. (SHEET S2 SHOWS COMPARTMENT
 DOORS AT 2'6' WIDTH, HOWEVER MINIMUM DOOR WIDTH IS 32"-
 SECTION- SECTIONS 604.8.1.2 & 404.2.3 FBC ACC. PLEASE
 UPDATE SHEET S1 WHICH STILL SHOWS THE DOORS SWINGING
 IN.)
  
 E) FAILED. PROVIDE THE WIDTH MEASUREMENT BETWEEN THE
 NEW MEN'S COMPARTMENT PARTION AND THE NEW URINAL
 PARTION- SECTION 405.3.5. (SHEET S2 SHOWS 1'11" CLEAR
 WIDTH FOR THE URINAL STALL, HOWEVER URINALS SHALL NOT
 BE CLOSER THAN 15 INCHES FROM CENTER TO SIDE WALL OR
 PARTITION- SECTION 405.3.1 FBC P. PLEASE NOTE THAT
 ACCESSIBLE URINALS SHALL HAVE 30X48-INCH CLEAR FLOOR
 SPACE APPROACHES- SECTION 605.3 FBC ACC. IS THE URINAL
 INTENDED TO BE ACCESSIBLE?).
  
 F) FAILED. REFER TO SECTION 604.8 AND PROVIDE THE MEN'S
 WATER CLOSET CLEAR FLOOR SPACE WIDTH DIMENSION IN THE
 DRAWING. (SHEET S2 SHOWS DEFICIENT CLEAR FLOOR SPACE-
 MINIMUM 60 INCHES MEASURED PERPENDICULAR FORM THE SIDE
 WALL AND 56 INCHES MEASURED PERPENDICULAR FROM THE REAR
 WALL ? SECTION 604.3.1 FBC ACC.
  
 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEM
 D.
  
 D) SHEET P-2: THE REVISED CALCULATION IS INCORRECT. THE
 GPM FLOW RATE IS 150.3 AT 75% CAPACITY IN ACCORDANCE
 WITH THE PDI METHOD. THE DESIGNER HAS INCORRECTLY
 REDUCED THAT RATE BY 25% DOWN TO 112.7 GPM WHICH IS NOT
 IN COMPLIANCE. PLEASE SELECT A GREASE INTERCEPTOR THAT
 HAS THE REQUIRED CAPACITY AND INDICATE THE MAKE AND
 MODEL ON THE PLAN. PLEASE NOTE SHEET P1 SHOWS A
 REPLACED INTERCEPTOR AND P2 SHOWS AN EXISTING 50 GPM
 INTERCEPTOR. PLEASE NOTE MANUFACTURER'S SPECIFICATIONS
 FOR A "DRAIN-NET TECHNOLOGIES APGI SERIES INTERCEPTOR"
 HAVE BEEN SUBMITTED, HOWEVER THWE CUT SHEET DOES NOT
 INDICATE THE SELCTED MODEL TO BE INSTALLED AND DOES NOT
 INDICATE THE PRODUCT HAS BEEN DESIGNED AND TESTED IN
 ACCORDANCE WITH THE LISTING STANDARDS UNDER SECTION
 1003.3.4 FBC P- ASME A112.14.3, ASME A112.14.4, CSA
 B481.1, PDIG101, OR PDI G102.
  
 6) FAILED. P1 & P2: THE ISOMETRIC SHOWS TWO EXPANSION
 TANKS BOTH OF WHICH ARE NOT IN THE CORRECT LOCATIONS.
 IF INSTALLING AN EXPANSION TANK IT SHALL BE LOCATED ON
 THE COLD WATER INLET PIPE DOWNSTREAM OF ALL CHECK
 VALVES, OR PRV'S- SECTION 607.3 FBC P.
  
 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A
 LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE
 WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A
 MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A
 PIPING DETAIL ON THE PLAN FOR INSTALLATION. DUE TO THE
 INCONSISTENCY OF THE DETAILS IT IS NOT CLEAR HOW
 TEMPERED WATER WILL BE PROVIDED TO THE LAVATORIES-
 PLEASE COMPLY AND NOTE THE REVISED WATER ISOMETRIC
 SHOWS A MASTER MIXNG VALVE AND A MIXING VALVE AT THE
 3-COMPARTMENT SINK. PLEASE INDICATE THE TEMPERATURE OF
 THE HOT WATER BEING SUPPLIED TO THE 3-COMPARTMENT SINK
 AND MOP SINK- SEE SECTION 607.1 FBC P.
  
 NEW COMMENTS BASED ON REVISED SHEETS.
  
 1) SHEET S2: PLEASE SHOW THE CENTERLINE OF THE TOILET
 PAPER DISPENSER AT 7-9 INCHES MEASURED FROM THE FRONT
 OF THE WATER CLOSET- SECTION AND FIGURE 604.7 FBC ACC.
  
 2) P-1: THE INDIRECT WASTE DETAIL FOR THE 3-COMPARTMENT
 SINK IS INCORRECT. EACH WELL OF THE SINK SHALL
 DISCHARGE INDEPENDENTLY TO THE FLOOR SINK- SECTION
 802.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER