| 2021-11-30 08:37:32 | 4TH REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21041585 |
| | 11/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST, 2ND, AND 3RD REVIEWS ARE LISTED BELOW WITH |
| | ADDITIONAL NOTES IN CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED ITEMS C, E, & F- SEE BELOW. |
| | |
| | C) FAILED. SHOW THE WIDTH OF THE NEW COMPARTMENT DOORS- |
| | SECTION 404.2.3 FBC ACC. (SHEET S2 SHOWS COMPARTMENT |
| | DOORS AT 2'6' WIDTH, HOWEVER MINIMUM DOOR WIDTH IS 32"- |
| | SECTION- SECTIONS 604.8.1.2 & 404.2.3 FBC ACC. PLEASE |
| | UPDATE SHEET S1 WHICH STILL SHOWS THE DOORS SWINGING |
| | IN.) |
| | |
| | E) FAILED. PROVIDE THE WIDTH MEASUREMENT BETWEEN THE |
| | NEW MEN'S COMPARTMENT PARTION AND THE NEW URINAL |
| | PARTION- SECTION 405.3.5. (SHEET S2 SHOWS 1'11" CLEAR |
| | WIDTH FOR THE URINAL STALL, HOWEVER URINALS SHALL NOT |
| | BE CLOSER THAN 15 INCHES FROM CENTER TO SIDE WALL OR |
| | PARTITION- SECTION 405.3.1 FBC P. PLEASE NOTE THAT |
| | ACCESSIBLE URINALS SHALL HAVE 30X48-INCH CLEAR FLOOR |
| | SPACE APPROACHES- SECTION 605.3 FBC ACC. IS THE URINAL |
| | INTENDED TO BE ACCESSIBLE?). |
| | |
| | F) FAILED. REFER TO SECTION 604.8 AND PROVIDE THE MEN'S |
| | WATER CLOSET CLEAR FLOOR SPACE WIDTH DIMENSION IN THE |
| | DRAWING. (SHEET S2 SHOWS DEFICIENT CLEAR FLOOR SPACE- |
| | MINIMUM 60 INCHES MEASURED PERPENDICULAR FORM THE SIDE |
| | WALL AND 56 INCHES MEASURED PERPENDICULAR FROM THE REAR |
| | WALL ? SECTION 604.3.1 FBC ACC. |
| | |
| | 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEM |
| | D. |
| | |
| | D) SHEET P-2: THE REVISED CALCULATION IS INCORRECT. THE |
| | GPM FLOW RATE IS 150.3 AT 75% CAPACITY IN ACCORDANCE |
| | WITH THE PDI METHOD. THE DESIGNER HAS INCORRECTLY |
| | REDUCED THAT RATE BY 25% DOWN TO 112.7 GPM WHICH IS NOT |
| | IN COMPLIANCE. PLEASE SELECT A GREASE INTERCEPTOR THAT |
| | HAS THE REQUIRED CAPACITY AND INDICATE THE MAKE AND |
| | MODEL ON THE PLAN. PLEASE NOTE SHEET P1 SHOWS A |
| | REPLACED INTERCEPTOR AND P2 SHOWS AN EXISTING 50 GPM |
| | INTERCEPTOR. PLEASE NOTE MANUFACTURER'S SPECIFICATIONS |
| | FOR A "DRAIN-NET TECHNOLOGIES APGI SERIES INTERCEPTOR" |
| | HAVE BEEN SUBMITTED, HOWEVER THWE CUT SHEET DOES NOT |
| | INDICATE THE SELCTED MODEL TO BE INSTALLED AND DOES NOT |
| | INDICATE THE PRODUCT HAS BEEN DESIGNED AND TESTED IN |
| | ACCORDANCE WITH THE LISTING STANDARDS UNDER SECTION |
| | 1003.3.4 FBC P- ASME A112.14.3, ASME A112.14.4, CSA |
| | B481.1, PDIG101, OR PDI G102. |
| | |
| | 6) FAILED. P1 & P2: THE ISOMETRIC SHOWS TWO EXPANSION |
| | TANKS BOTH OF WHICH ARE NOT IN THE CORRECT LOCATIONS. |
| | IF INSTALLING AN EXPANSION TANK IT SHALL BE LOCATED ON |
| | THE COLD WATER INLET PIPE DOWNSTREAM OF ALL CHECK |
| | VALVES, OR PRV'S- SECTION 607.3 FBC P. |
| | |
| | 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A |
| | LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE |
| | WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A |
| | MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A |
| | PIPING DETAIL ON THE PLAN FOR INSTALLATION. DUE TO THE |
| | INCONSISTENCY OF THE DETAILS IT IS NOT CLEAR HOW |
| | TEMPERED WATER WILL BE PROVIDED TO THE LAVATORIES- |
| | PLEASE COMPLY AND NOTE THE REVISED WATER ISOMETRIC |
| | SHOWS A MASTER MIXNG VALVE AND A MIXING VALVE AT THE |
| | 3-COMPARTMENT SINK. PLEASE INDICATE THE TEMPERATURE OF |
| | THE HOT WATER BEING SUPPLIED TO THE 3-COMPARTMENT SINK |
| | AND MOP SINK- SEE SECTION 607.1 FBC P. |
| | |
| | NEW COMMENTS BASED ON REVISED SHEETS. |
| | |
| | 1) SHEET S2: PLEASE SHOW THE CENTERLINE OF THE TOILET |
| | PAPER DISPENSER AT 7-9 INCHES MEASURED FROM THE FRONT |
| | OF THE WATER CLOSET- SECTION AND FIGURE 604.7 FBC ACC. |
| | |
| | 2) P-1: THE INDIRECT WASTE DETAIL FOR THE 3-COMPARTMENT |
| | SINK IS INCORRECT. EACH WELL OF THE SINK SHALL |
| | DISCHARGE INDEPENDENTLY TO THE FLOOR SINK- SECTION |
| | 802.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |