| 2021-11-30 09:42:35 | 4TH REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21041585 |
| | 11/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST, 2ND, AND 3RD REVIEWS ARE LISTED BELOW WITH |
| | ADDITIONAL NOTES IN CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED- GAS ISOMETRIC- SHEET P2: IT APPEARS THAT AN |
| | 1-1/4-INCH SCHEDULE 40 METALLIC PIPE WILL BE THE MAIN |
| | LOW PRESSURE SUPPLY PIPE HOWEVER IT IS MISLABELED AS A |
| | SCHEDULED 40 PVC SLEEVE- PLEASE CORRECT. |
| | |
| | 2) FAILED. NEW MANUFACTURER'S SPECIFICATIONS HAVE BEEN |
| | SUBMITTED FOR A DIRECT VENT CONDENSING TANKLESS WATER |
| | HEATER. THE SPECS INDICATE A COMBUSTION AIR INTAKE DUCT |
| | AND A VENT DUCT TO RUN TO TRE EXTERIOR OF THE BUILDING. |
| | PLEASE INDICATE THE TYPE AND SIZE OF INTAKE DUCT AND |
| | SHOW THE DUCT TERMINATION LOCATIONS ON THE EXTERIOR OF |
| | THE BUILDING ON SHEETS P1 AND M1. PLEASE INCLUDE |
| | CLEARANCE DISTANCE MEASUREMENTS FROM THE WATER HEATER |
| | EXHAUST DUCT TO MECHANICAL AND GRAVITY AIR INTAKES INTO |
| | THE BUILDING INCLUDING THE NEW COMBUSTION AIR FAN INLET |
| | OPENING- SECTION 503.8 (5) FBC FG. |
| | |
| | 2A) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW |
| | WATER HEATER- SHOW TYPE AND SIZE OF PIPE AND DISCHARGE |
| | LOCATION- SECTION 307.2 FBC FG. |
| | |
| | 3) FAILED. SHEET M1: PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE NEW FAN BASED ON SECTION 304.9 FBC |
| | FG- 0.35 CFMS PER 1000 BTUH OF THE APPLIANCES. A) SHOW |
| | MEANS OF PROVIDING APPLIANCE INTERLOCK WITH THE FAN- |
| | SECTION 304.9.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |