| 2021-10-04 10:35:11 | 3RD REVIEW FBC-2020 MECHANICAL | | | PERMIT-21041585 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE KITCHEN OUTSIDE AIR CALCULATION MUST | | | BE CALCULATED USING THE KITCHENS FIGURES UNDER THE FOOD | | | AND BEVERAGE SERVICE OCCUPANCY CLASSIFICATION IN FBC M | | | TABLE 403.3.1.1 | | | 1029 CFM?S/1000 = 1.029 X 20 X 7.5 = 154.35; 1029 X .12 | | | = 123.48; 154.35 + 123.48 = 278 CFM?S OF REQUIRED | | | OUTSIDE AIR. 1029 X .7 = 720 CFM?S OF REQUIRED EXHAUST | | | AIR FOR THE KITCHEN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|